7.2.1 Example of order no. 1<br />

Line feeder breaker for LRT substation in Europe; comply with EN50123, with breaking<br />

capacity of 50 kA, configured as follows:<br />

1. Load current of 4000 A.<br />

2. Nominal voltage of 1500 V; 2x2 arc chute chosen due to high breaking<br />

capacity up to 70 kA.<br />

3. Auxiliary supply voltage of 230 VAC for closing solenoid;<br />

4. Vertical layout of both main terminals (V/V);<br />

5. Breaker polarization not important;<br />

6. Without SEL unit (not available with special terminals);<br />

7. With OC release, adjustable in range of 6 kA…12 kA, with 7 marks on the scale<br />

every 1 kA, set at 9 kA;<br />

8. Auxiliary supply voltage of 230 VAC for controls;<br />

9. With 8 auxiliary contacts;<br />

10. With OC trip target;<br />

11. With zero voltage release (UVR);<br />

12. Without electrodynamic tripping device;<br />

13. With forced tripping release for withdrawal operations;<br />

14. With contacts’ position indicator;<br />

15. Without sidewalls’ protection;<br />

16. With hand lever;<br />

17. Without arc chute indicator;<br />

18. Counter not available;<br />

19. With standard control connectors;<br />

20. Test report according to EN50123-2 standard.<br />

Correct catalogue code shall be: 2 3 A 4 0 0 2 5 R 1 6 0 1 1 0 1 0 0 1 1<br />

General remarks:<br />

Please check the “Unlock On Request options” checkbox to enable entering values,<br />

which are not listed in this form.<br />

Please always define the markings number and values for OC release.<br />

Please choose the “On Request” option to define own OC tripping range.<br />

Use “On Request” option if available to define own, not standard ratings.<br />

Any other than first option for connector type are usually dedicated for retrofit<br />

purposes. Please refer to special type of connectors’ options 2,3,4,R before<br />

choosing these. Option 1 is suitable for most applications.<br />

2012-11-21 S47183R01E06 Design and specifications are subject to change without notice 53