Fig. 55-4 Unscrew all the plugs from control boards<br />

Fig. 55-7 Pay attention, that no cables will be pinched<br />

between box and front cover during closing!<br />

Fig. 55-5 Pull out the plugs of the control boards. Pull out<br />

selected control board. Insert new control board<br />

<br />

Listen that both, the isolation plate at the side of<br />

equipment and the isolation plate at the side of<br />

soldering, were inserted!<br />

Fig. 55-8 Carefully replace the control box front cover and<br />

attach the with the four screws<br />

<br />

Put on plugs X2…X6, fix the screws of the plugs and<br />

switch on control voltage.<br />

Checking the breaker:<br />

<br />

Open and Close the breaker 3 times while it is<br />

disconnected from the system (in the “Test-position“ of<br />

the draw out version/the installation). The breaker must<br />

open and close without a time delay over 400 ms.<br />

<br />

If the test succeeds, reconnect the breaker to the main<br />

circuit.<br />

Fig. 55-6 Plug in all control plugs and tighten it by the<br />

screws.<br />

2012-11-21 S47183R01E06 Design and specifications are subject to change without notice 47