4.3.2 <strong>Controls</strong> supply circuit<br />

Breaker<br />

External<br />

power supply<br />

+ / ~<br />

AC 115-240V ±10%<br />

DC 35-350V ±10%<br />

- / N<br />

-X3<br />

[ 4 ]<br />

[ 5 ]<br />

-X10<br />

[ 1 ]<br />

[ 3 ]<br />

[ 10 ]<br />

[ 9 ]<br />

[ 8 ]<br />

[ 7 ]<br />

[ 6 ]<br />

+DC 24 V ±2%<br />

GND<br />

Breaker<br />

External<br />

power supply<br />

+<br />

DC 24 V ±5%<br />

-X3<br />

[ 4 ]<br />

-X11<br />

[ 1 ]<br />

[ 10 ]<br />

[ 9 ]<br />

[ 8 ]<br />

+DC 24 V ±2%<br />

-<br />

[ 5 ]<br />

[ 3 ]<br />

[ 7 ]<br />

[ 6 ]<br />

GND<br />

36/ X _ _ _ _ _ _<br />

Key position - 2<br />

Key number – 1: Voltage converter DC 35-85 V ; DC 88-145 V ; DC 125-353 V ;AC 115-240 V<br />

Key number – 2: Interface for direct external voltage DC 24 V +/- 5% connection.<br />

Fig. 23 Supply with voltage converter or with direct external 24 V DC ±5%.<br />

18 Design and specifications are subject to change without notice S47183R01E06 2012-11-21