With correctly designed interlock in enclosure, FTU provides<br />

safety-tripping function. The breaker is tripped BEFORE its<br />

terminals are disconnected from mains, during withdraw<br />

operation of the trolley.<br />

Bottom view<br />

Fig. 11b Opening operation by using hand lever<br />

3.2.9 Auxiliary switches (code nr: 9)<br />

• The breaker can be equipped with 3, 5 or 10 isolated,<br />

form C, auxiliary switches (1 NO/NC each). The movable<br />

main arm activates the contacts.<br />

• The contacts are wired to 15-pin control terminals: -X4<br />

and -X5; 5 switches to each terminal.<br />

• Maximum electrical ratings for switches are 5A/230VAC<br />

and 0.3A/220V<strong>DC</strong>. Utilization category AC/<strong>DC</strong> 12 and 13.<br />

Fig. 10b Positioning of the forced tripping pin<br />

3.2.8 Hand lever (code nr: 16)<br />

• Optionally, hand lever for manual closing and opening<br />

operation during maintenance is available. This tool<br />

must not be use while breaker is alive!<br />

• To close the contacts, install hand lever on the drive’s<br />

rod, and pull it smoothly until latches snap [Fig. 11a].<br />

• To open the contacts, install the tool into the ring and<br />

push it hard against the drive’s rod until breaker opens<br />

[Fig. 11b].<br />

Fig. 12 Auxiliary contacts layout in control box<br />

ring<br />

Fig. 11a Closing operation by using hand lever<br />

(~45 lbf)<br />

3.2.10 Indicators<br />

Optionally, the circuit breaker can be equipped with following<br />

indicators:<br />

• POSITION INDICATOR (code nr: 14) - is mounted at the<br />

front of the closing drive. It’s mechanically switched by<br />

means of drive’s rod position. It indicates position of the<br />

main contacts. “O” – means contacts are open; “I” –<br />

means contacts are closed [Fig. 13].<br />

• OCT INDICATOR (code nr: 10) – electrical switch, the<br />

same type as in 3.2.7, mounted at the top of OCT [Fig.<br />

14]. It’s potential free, NO contact, which provides signalization<br />

of the OCT tripping.<br />

• ARC CHUTE INDICATOR (code nr: 17) – electrical switch,<br />

the same type as in 3.2, mounted on the sidewall. Indicates<br />

presence of the arc chute and blocking closing<br />

drive until arc chute is installed [Fig. 15].<br />

S47183-e 01/2008 Design and specifications are subject to change without notice 9