3. Technical informations<br />

3.1 Introduction<br />

• Gerapid is a high-speed <strong>DC</strong> circuit breaker. This is a single-pole<br />

<strong>DC</strong> breaker, primarily designed for use in railway<br />

propulsion-power distribution systems with operating<br />

currents up to 8000A (code nr: 1) and operating voltages<br />

up to 3600V (code nr: 2). Additional application areas<br />

are special industrial plants as electrolysis plants,<br />

mines or steel mills.<br />

• The breaker type Gerapid has a very high interruption<br />

capacity combined with a current limiting characteristic.<br />

The arc chute works on the basis of an asbestos-free arc<br />

splitting principle.<br />

• A wide variety of accessories and spares are available<br />

for maintenance, repair, or as a possible extension. The<br />

breaker shall be configured by using PST coding system,<br />

available at the end of this instruction or as an excel<br />

file, free of charge.<br />

• Closing of the circuit breaker is performed through a<br />

high-power solenoid drive (code nr: 3).<br />

• During inspections, opening and closing may be carried<br />

out by means of a hand lever (code nr: 16), which is<br />

mounted onto the armature of the closing drive.<br />

• Overload tripping is obtained directly via OCT device<br />

(code nr: 7) or, optionally by electro-dynamic coil (code<br />

nr: 12). Indirect remote tripping can be achieved by<br />

means of a shunt trip or exclusively, by a zero voltage<br />

release (code nr: 11).<br />

• Gerapid breakers have a compact and enclosed construction<br />

[Fig. 4]. They are IP 00 protected. All parts are<br />

mounted on thick-walled, non-breakable and fireproof<br />

insulation panels.<br />

3.2 Components and accessories<br />

3.2.1 Contact system<br />

• Gerapid breakers are equipped with a two-stage contact<br />

system [Fig. 5], consists of a main contact and an<br />

arcing contact. With this proven design of the contact<br />

system, the main contact is not subjected to any wear or<br />

tear.<br />

• The main contacts are coated with a silver, composite<br />

material. The arcing contact and link braid are made<br />

from copper and can be easily replaced.<br />

• The flexible bend is linked to the arcing contact by<br />

means of very tight braid.<br />

Braid<br />

Flexible band<br />

Arc runner<br />

Arcing contact<br />

Main contact<br />

Fig. 5 Contact system: new (upper) and old (lower) type<br />

3.2.2 Arc chute (code nr: 2)<br />

Fig. 4 Modular construction overview<br />

• Compact and modular design of the arc system requires<br />

no additional magnetic support and allows smaller<br />

safety distances with high breaking capacity.<br />

• Because of the new compact dimensions these breakers<br />

can be installed in extremely small enclosures (from<br />

600mm; 2ft) and offers a cost-effective solution for replacements.<br />

• An adaptor is used to mount the various arc chutes for<br />

different operating voltages to the breakers.<br />

• The arc chutes consist of a highly durable, arc-proof material,<br />

wherein the arc plates have been integrated.<br />

• The arc plates split the arc into partial arcs and increase<br />

the arcing voltage by multiplying the anode and cathode<br />

voltage drop. Because of their high heat capacity,<br />

the plates and arc chute walls absorb a large amount of<br />

the arc’s energy.<br />

6 Design and specifications are subject to change without notice S47183-e 01/2008