3. Technical informations<br />
3.1 Introduction<br />
• Gerapid is a high-speed <strong>DC</strong> circuit breaker. This is a single-pole<br />
<strong>DC</strong> breaker, primarily designed for use in railway<br />
propulsion-power distribution systems with operating<br />
currents up to 8000A (code nr: 1) and operating voltages<br />
up to 3600V (code nr: 2). Additional application areas<br />
are special industrial plants as electrolysis plants,<br />
mines or steel mills.<br />
• The breaker type Gerapid has a very high interruption<br />
capacity combined with a current limiting characteristic.<br />
The arc chute works on the basis of an asbestos-free arc<br />
splitting principle.<br />
• A wide variety of accessories and spares are available<br />
for maintenance, repair, or as a possible extension. The<br />
breaker shall be configured by using PST coding system,<br />
available at the end of this instruction or as an excel<br />
file, free of charge.<br />
• Closing of the circuit breaker is performed through a<br />
high-power solenoid drive (code nr: 3).<br />
• During inspections, opening and closing may be carried<br />
out by means of a hand lever (code nr: 16), which is<br />
mounted onto the armature of the closing drive.<br />
• Overload tripping is obtained directly via OCT device<br />
(code nr: 7) or, optionally by electro-dynamic coil (code<br />
nr: 12). Indirect remote tripping can be achieved by<br />
means of a shunt trip or exclusively, by a zero voltage<br />
release (code nr: 11).<br />
• Gerapid breakers have a compact and enclosed construction<br />
[Fig. 4]. They are IP 00 protected. All parts are<br />
mounted on thick-walled, non-breakable and fireproof<br />
insulation panels.<br />
3.2 Components and accessories<br />
3.2.1 Contact system<br />
• Gerapid breakers are equipped with a two-stage contact<br />
system [Fig. 5], consists of a main contact and an<br />
arcing contact. With this proven design of the contact<br />
system, the main contact is not subjected to any wear or<br />
tear.<br />
• The main contacts are coated with a silver, composite<br />
material. The arcing contact and link braid are made<br />
from copper and can be easily replaced.<br />
• The flexible bend is linked to the arcing contact by<br />
means of very tight braid.<br />
Braid<br />
Flexible band<br />
Arc runner<br />
Arcing contact<br />
Main contact<br />
Fig. 5 Contact system: new (upper) and old (lower) type<br />
3.2.2 Arc chute (code nr: 2)<br />
Fig. 4 Modular construction overview<br />
• Compact and modular design of the arc system requires<br />
no additional magnetic support and allows smaller<br />
safety distances with high breaking capacity.<br />
• Because of the new compact dimensions these breakers<br />
can be installed in extremely small enclosures (from<br />
600mm; 2ft) and offers a cost-effective solution for replacements.<br />
• An adaptor is used to mount the various arc chutes for<br />
different operating voltages to the breakers.<br />
• The arc chutes consist of a highly durable, arc-proof material,<br />
wherein the arc plates have been integrated.<br />
• The arc plates split the arc into partial arcs and increase<br />
the arcing voltage by multiplying the anode and cathode<br />
voltage drop. Because of their high heat capacity,<br />
the plates and arc chute walls absorb a large amount of<br />
the arc’s energy.<br />
6 Design and specifications are subject to change without notice S47183-e 01/2008