13.11.2013 Views

High Speed DC Circuit Breaker - G E Power Controls

High Speed DC Circuit Breaker - G E Power Controls

High Speed DC Circuit Breaker - G E Power Controls

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

2.2 Installation<br />

2.2.1 Operational environment<br />

• The breaker, as delivered, is IP00 protected. It is intended<br />

to work in indoor applications, without pollutions, with<br />

non-conductive dust, protected against high humidity<br />

and condensation. Low conductivity dust deposit due to<br />

frequent condensation of humidity is acceptable. General<br />

environmental conditions refer to EN 50123-1 - annex<br />

B, and IEC60947, class PD3.<br />

• The breaker can operate within ambient temperature<br />

range of –5°C…+40°C (23...104°F). With decreased nominal<br />

current, breaker can operate up to +60°C (140°F).<br />

• The breaker can operate at altitude up to 2000m<br />

(~6500ft).<br />

• The breaker shall not be subjected to strong vibrations.<br />

Vibrations of 0.5g per 30sec in vertical and horizontal directions<br />

are allowed.<br />

• Air shall be clean and its relative humidity shall be not<br />

more than 50 % r.h. at the maximum temperature of<br />

+40°C (104°F). Relative humidity may be higher if the<br />

temperatures are lower, for example, 90 %r.h. at +20°C<br />

(68°F). Slight condensation might occur during variations<br />

of temperature<br />

2.2.2 Installation and interfaces<br />

• The lower and upper connections (code nr: 4) must be<br />

connected directly to the main cables or bus bars. The<br />

breaker must only be used in an upright operation position<br />

with the arc chute in place and fully secured.<br />

• After installation, both the arc chute and special<br />

threaded joints must be checked for tightness.<br />

• The safety distances as shown in the dimensional drawings<br />

must be maintained to grounded or insulated parts.<br />

Suitable measures must be taken to protect personnel<br />

from arcs.<br />

• Strong, external magnetic fields, caused by improperly<br />

located supply conductors or tray fields from other devices,<br />

can lead to a shift of the trip setting thresholds.<br />

This may result in premature tripping, or no tripping at<br />

al, during low-level short circuit current events. This has<br />

to be accounted for when installing and operating the<br />

device with shielding added if appropriate.<br />

• The control wires must be connected to the control terminals<br />

(code nr: 19), as shown in the schematic circuit<br />

diagram (Page 14). The protective grounding wire must<br />

be connected at the marked contact.<br />

2.3 Usage<br />

2.3.1 Supply and load<br />

• In accordance with its type, the breaker has been designed<br />

for the current and voltage listed in Table 1, section<br />

3.3.<br />

• During continuous operation, breaker must be loaded<br />

with its rated current at maximum. Load currents in excess<br />

of breaker nameplate rating are allowable for brief<br />

periods. Refer to the short time currents listed in Tables<br />

1a/1b.<br />

• Do not exceed the rated operating voltage shown on the<br />

breaker’s nameplate.<br />

• The drive and the auxiliary tripping devices (code nr: 8).<br />

shall be supply within the specified control voltage<br />

range. The auxiliary-tripping devices must be loaded<br />

with the values listed in Table 2a at maximum.<br />

• Plugging or removing the auxiliary current connectors<br />

are only allowed at zero potential, no voltage (-X2<br />

:1/:2) (-X3 :4/:5) !<br />

2.3.2 Adjusting the OCT<br />

• OCT is an over-current tripping device (code nr: 7), which<br />

trips a breaker in case of overload or short circuit. This is<br />

fully adjustable, instantaneous and direct tripping device.<br />

• OCT adjustment [Fig.3], within a specific range, is realized<br />

by turning the screw 1.<br />

• Adjusting procedure requires an SW6 hexagon wrench<br />

2.<br />

• The adjustment must only be carried out after the<br />

breaker has been disconnected from the main circuit<br />

and has been grounded.<br />

• Turning the adjustment screw clockwise increased the<br />

trip threshold, turning the screw counter-clockwise decreased<br />

the tripping threshold.<br />

• Aligning the arrow and the marking into one line 3 performs<br />

adjustment.<br />

S47183-e 01/2008 Design and specifications are subject to change without notice 5

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!