D) Install the adapter<br />

• [Fig. 48]. Install two protective walls (3). Use new ones<br />

if necessary. Install two parings of adapter (2) and<br />

tighten screws (1); use 5Nm [44lbf*in].<br />

4b<br />

E) Install the arc chute<br />

• [Fig. 49]. Put in arc chute (1) into adapter (2).<br />

• [Fig. 49]. Tighten front- and backside connections of<br />

the arc arc runners (3), including lock washer; use<br />

10Nm [88lbf*in].<br />

• [Fig. 49]. Tighten front- and backside of the arc chute<br />

connections (4), including flat washers; use 5Nm<br />

[44lbf*in].<br />

4<br />

5<br />

4a<br />

1 3<br />

5a<br />

6<br />

6a<br />

2<br />

Fig. 48 Adapter and protective walls<br />

1<br />

8<br />

7<br />

9<br />

2<br />

4<br />

3<br />

5<br />

10<br />

Fig. 49 Arc chute and arc runners fixing<br />

Fig. 50 Changing pre-arcing contact.<br />

S47183-e 01/2008 Design and specifications are subject to change without notice 41