1.2 Safety hints<br />

1.2.1 Securing against falling parts<br />

Hint 1: Place a cloth into the lower area of the pre-arcing<br />

contact [Fig. 1]. Remember to secure the closing drive<br />

according to Hint 3.<br />

2. General usage conditions<br />

2.1 Transportation<br />

• The breaker is transported on wooden palette. It is fixed<br />

by shrunken plastic film. A paper cardboard box covers<br />

the breaker on the palette. Truck, railway, airplane and<br />

ship transport is possible. In case of sea transport, special<br />

protection against salty and humid environment is<br />

used.<br />

• The circuit breaker must always be transported to the<br />

installation site vertically and fully packed. The packaging<br />

protects the device against damage and dust; it<br />

should only be removed prior to installation.<br />

• If the packaging is damaged, the breaker and the arc<br />

chute must be inspected for damage. Ensure that all<br />

packaging materials have been carefully removed prior<br />

to breaker installation.<br />

• For handling the unpacked breaker [Fig. 3], use a transportation<br />

belts and reach them below the closing drive<br />

(a) and below the lower terminal (b).<br />

• Listen, that the basement isolation of the unpacked<br />

breaker during handling will not be damaged (for example<br />

don’t push the breaker back and forth at rough surface).<br />

Fig.1 Protecting of the arcing area aginst falling parts<br />

1.2.2 Maintenance with zero voltage release<br />

Hint 2: In case, when the zero voltage release is installed<br />

in, it shall be energized to enable closing of the breaker.<br />

Only then maintenance of the pre-arcing contacts is<br />

possible.<br />

Hint 3: To prevent the risk of injury, it is recommended to<br />

secure the close position of the breaker with a mechanical<br />

interlock device [Fig. 2]. The tube shall have ~50mm<br />

[~2in] length and inner diameter of minimum 14mm<br />

[0,55in]. The outer diameter of the locking rod shall be<br />

less 8mm [0,3in]. GE does not offer this locking device.<br />

a<br />

b<br />

Closing drive<br />

Secure tube<br />

Locking rod<br />

SW 6<br />

Fig. 2 Securing closing drive against opening<br />

Fig. 3 Handling the breaker and setting of the OCT unit<br />

4 Design and specifications are subject to change without notice S47183-e 01/2008