Control box terminals 1x12-pole AC 400V, 20A<br />
4x15-pole<br />
AC 250V, 8A<br />
Closing solenoid drive 1) Rated voltage AC 48V…230V and <strong>DC</strong> 48V…220V<br />
Operating range<br />
80%...115% of rated voltage<br />
<strong>Power</strong> consumption Gerapid 2607 / 4207 1750W / 2000W<br />
<strong>Power</strong> consumption Gerapid 6007 / 8007 2600W / 2600W<br />
Minimal CLOSING command duration<br />
100ms<br />
min.interval between two "CLOSE" operations ~8s with NEKO installed; ~14s w/o NEKO<br />
Internal voltage converter 1) Input: Voltage range <strong>DC</strong> 33...85V<br />
for Gerapid 2607, 4207, 6007, 8007 Output: Voltage range <strong>DC</strong> 24V (±5%)<br />
Current<br />
6A permanent<br />
Model description<br />
PCMD 150 48 S24W-GE<br />
Input: Voltage range <strong>DC</strong> 88...145V<br />
Output: Voltage range <strong>DC</strong> 24V (±5%)<br />
Current<br />
6A permanent<br />
Model description<br />
nr. PCMD 150 110 S24W-GE<br />
Input: Voltage range AC 115...290V, <strong>DC</strong> 125...353V<br />
Output: Voltage range <strong>DC</strong> 24V (±5%)<br />
Current<br />
3A permanent, 5A/100ms<br />
Model description<br />
nr. PCMA 70 S24W-GE<br />
External power supply with plug and socket unit requires extrnal 24V (±5%) <strong>DC</strong><br />
Aux. contact HS 1…HS 10, Rated operational voltage Ue/AC 230V<br />
OCT- and Arc chute- indicators Rated operational current Ie/AC-15 1A<br />
Rated operational current Ie/AC-12 (Ith) 10A<br />
Rated operational voltage Ue/<strong>DC</strong> 110V<br />
Rated operational current Ie/<strong>DC</strong>-13 0,5A<br />
Contact duty (min. value)<br />
<strong>DC</strong> 10V/2 mA<br />
ST 1) Rated voltage Uc 24V<br />
(Shunt trip) Operating range: OFF 21.6V…26.4V<br />
<strong>Power</strong> consumption<br />
~ 150W<br />
UVR 1) Rated voltage Uc 24V<br />
(Zero voltage release) Operating range: OFF < 3V<br />
Operating range: ON 24V (±10%)<br />
<strong>Power</strong> consumption<br />
~ 40W<br />
ED-tripping device 1) Energie source: Capacity 2000µF<br />
Charging voltage<br />
300V<br />
Switching interval<br />
max. 2/min with 10 consecutive operations<br />
Endurance<br />
1000 operations with 1operation per 180s<br />
Firing signal 2) level / duration 6…24V / 100…1000ms<br />
1) Standard ambient conditions acc. to EN 123-1 Attachement B. For meeting outside of this standard range, please call back.<br />
Table 2a: Technical data of auxiliary circuits<br />
Components<br />
Technical datas of control circuits<br />
Us / In<br />
SU-Control CLOSE-push-button -S1 <strong>DC</strong> 24V / approx. 10mA<br />
ST releasing push-button-S2 <strong>DC</strong> 24V / approx. 4A<br />
UVR releasing push-button -S2 ( -X2 :6 / :7) <strong>DC</strong> 24V / approx. 10mA<br />
push-button -S2 ( -X2 :8 / :9 )<br />
<strong>DC</strong> 24V / approx. 450mA<br />
ED-coil tripping w/o NEKO (R = 4Ohm) push-button -S3 <strong>DC</strong> 300V / 750A / 3ms<br />
ED-coil tripping with NEKO Connect "Firing signal" at ( -X2 :10 / :11 ) <strong>DC</strong> 6V…24V / approx.20mA<br />
Table 2b: Control circuits ( directional values to rate the components )<br />
S47183-e 01/2008 Design and specifications are subject to change without notice 13