• The sensor includes Hall-probes and delivers a proportional<br />

signal-output to the SEL control. The signalprocessing<br />

unit transforms input signal, into standard<br />

output signals shown in the table below.<br />

• The outputs are insulated from the main voltage. The insulation<br />

withstands voltages up to 4kV RMS and up to<br />

40kV in peak.<br />

• Two versions are available. Standard model (T35) for<br />

ambient temperature -5°C…+35°C and the model for<br />

higher temperature (T55) -5°C…+55°C.<br />

• More details can be found in separate instruction for SEL<br />

usage.<br />

Type SEL 06-1 06-2 06-4 12-1 12-2 12-4<br />

Input - 6kA…+6 kA -12kA…+12kA<br />

U Ne[V] 1000 2000 4000 1000 2000 4000<br />

Fig. 19-1 NEKO control unit<br />

• (2) internal voltage converter (code nr: 8) - converts external<br />

supply voltage (-X3 :4/:5) to the internal 24V<strong>DC</strong>,<br />

required by controls (except for the drive supply).<br />

T35<br />

T55<br />

I Ne<br />

for ambient temperature of the breaker<br />

-5°C…+35°C / +23°F…+95°F<br />

for ambient temperature of the breaker<br />

-5°C…+55°C / +23°F...+131°F<br />

Relating to the rated current of the breaker<br />

Output<br />

4...20mA<br />

-20...20mA<br />

-10...10V<br />

U Ni[kV] 12 18 40 12 18 40<br />

3.2.13 Electronic control system<br />

All the control units are installed in control box [Fig. 18].<br />

Starting from the left, these are:<br />

Fig. 19-2 Voltage converter 110V/24V <strong>DC</strong><br />

• (3) SU control unit – see point 3.2.11.<br />

Fig. 19-3 SU control unit<br />

• (4) ST/UVR control unit – simple relays’ system. It controls<br />

operation of shunt trip or zero voltage release.<br />

Fig. 18 Control box with control units<br />

• (1) NEKO control unit [Fig. 19-1] – internal control unit<br />

with capacitors’ bank. It releases firing signal for ED coil<br />

(-X2 :10/:11) and enable signalization of the capacitors’<br />

charging (-X3 :6/:7). NEKO control unit also blocks the firing<br />

signal until C-bank is fully charged (~15sec).<br />

• NEKO unite requires high quality firing signal. Be sure,<br />

that voltage level is between 6V…24V and there is no<br />

short spikes on signal (