Position’s indicator<br />

Drive’s rod<br />

Fig. 13 Position indicator<br />

Knob<br />

Side protection<br />

Control cover box<br />

Closing drive<br />

Fig. 16 Solenoid closing drive and control box<br />

• In addition, the switch-in mechanism is electrically<br />

blocked for approximately 8sec. or 14sec. after activation<br />

(see Table 2a “Activating magnet”). This prevents<br />

premature activation following a short circuit.<br />

Fig. 14 OCT indicator<br />

3.2.12 Current measurement system (code nr: 6)<br />

• The SEL current measurement system consists of the<br />

sensing component (1) and signal-processing unit (2)<br />

[Fig.17]. SEL sensor is integrated into a specially shaped<br />

upper terminal of the breaker and is connected by a<br />

shielded cable to the signal-processing unit. SEL control<br />

unit is placed in the control-box [Fig. 18].<br />

Fig. 15 Arc chute indicator<br />

3.2.11 Solenoid closing drive (code nr: 3)<br />

• For normal closing operations, the breaker is fitted with<br />

a high power solenoid coil. The drive is mounted at the<br />

front of the breaker and is equipped with a grounded<br />

casing.<br />

• Closing drive is supplied independently from other controls<br />

(-X2 :1/:2), and directly from power source. Voltage<br />

level shall be defined at the order. Rated power depends<br />

of breaker type is between 1,8kW and 2,6kW.<br />

• CLOSING command is enable by potential free contact<br />

at (-X2 :4/:5) the signal durations shall be ~300ms.<br />

• The closing drive system always includes a self-interrupt<br />

control circuit (SU unit). This circuit enables a short activation<br />

with a time of ~150ms. SU unit switches power to<br />

the solenoid and automatically switched it off after<br />

~400ms.<br />

• SU unit prevents also repeated drive activation (antipumping),<br />

during continuous operation, due to an existing<br />

short circuit.<br />

(1) SEL sensor<br />

(2) SEL control<br />

unit<br />

Fig. 17 SEL current measurement system<br />

• SEL may be used for recording <strong>DC</strong> currents in selected<br />

measurement ranges of 6kA or 12kA. Measurement of<br />

rated current values and of the current rise may now be<br />

made directly at the breaker.<br />