UPS<br />

IEM - compared to legacy parallel system<br />

UPS 1<br />

100 kVA<br />

UPS 2<br />

100 kVA<br />

75%<br />

75%<br />

load 300 kVA<br />

load<br />

load = 100%<br />

07:00 18:00<br />

time<br />

Legacy Parallel System<br />

Full-Load Condition<br />

In full load condition the efficiency of a<br />

UPS is optimal. However, this condition<br />

only occurs typically 10 hours / day.<br />

UPS 3<br />

100 kVA<br />

75%<br />

efficiency<br />

4 UPS<br />

UPS 4<br />

100 kVA<br />

75%<br />

load %<br />

UPS 1<br />

100 kVA<br />

UPS 2<br />

100 kVA<br />

UPS 3<br />

100 kVA<br />

UPS 4<br />

100 kVA<br />

15%<br />

15%<br />

15%<br />

15%<br />

load 60 kVA<br />

load<br />

18:00 07:00<br />

efficiency<br />

4 UPS<br />

load = 20%<br />

load %<br />

time<br />

Legacy Parallel System<br />

Partial-Load Condition<br />

In partial load condition (most of the<br />

time) the efficiency of the UPS is lower<br />

causing higher energy costs.<br />

IEM<br />

A<br />

B<br />

X<br />

UPS 1<br />

100 kVA<br />

UPS 2<br />

100 kVA<br />

UPS 3<br />

100 kVA<br />

30%<br />

load 60 kVA<br />

load<br />

18:00 07:00<br />

efficiency<br />

2 UPS<br />

load = 20%<br />

time<br />

IEM<br />

Intelligent Energy Management<br />

Partial Critical Load Condition<br />

(UPS Redundancy)<br />

With IEM installed 2 units will be<br />

switched off automatically. In this<br />

way the efficiency is improved, still<br />

maintaining a n+1 redundant system.<br />

UPS 4<br />

100 kVA<br />

30%<br />

load %<br />

UPS 1<br />

100 kVA<br />

UPS 2<br />

100 kVA<br />

UPS 3<br />

100 kVA<br />

UPS 4<br />

100 kVA<br />

60%<br />

load 60 kVA<br />

load<br />

18:00 07:00<br />

efficiency<br />

1 UPS<br />

load = 20%<br />

load %<br />

time<br />

IEM<br />

Intelligent Energy Management<br />

Partial non-Critical Load<br />

Condition (Utility Redundancy)<br />

With IEM installed 3 units can be<br />

switched off. In this way the efficiency<br />

is improved even more. The bypass is<br />

still available and will supply the load in<br />

case of a failure.<br />

A.7