UPS<br />

Match Series - line-interactive UPS<br />

Applications<br />

The line-interactive Digital Energy Match Series UPS is used in a wide range<br />

of IT, networking and telecommunications applications. It will protect servers,<br />

hubs, switches and routers, and may also be installed to protect PCs, workstations,<br />

cash registers, fax machines, modems and ISDN adaptors.<br />

Order codes<br />

A<br />

B<br />

X<br />

Function<br />

Providing exceptional cost-critical<br />

protection for electrical equipment<br />

Standards / Marking<br />

Safety: EN 50091-1-1; EN 60950;<br />

IEC 60950<br />

EMC: EN 50091-2<br />

Characteristics<br />

The line-interactive Match Series UPS normally supplies the load through a<br />

bypass circuit. Filtering capabilities guard against surges, spikes and high<br />

frequency interferences. The utility also keeps the battery fully charged.<br />

The input voltage window is extremely wide: as long as the input voltage is<br />

within 165-275 Vac (Match 500-1500 VA) or even between 140-305 Vac (Match<br />

2200-3000 VA) the Automatic Voltage Regulation (AVR) guarantees an output<br />

voltage that is between 190-254 Vac and acceptable for every modern ICT<br />

device.<br />

In case of a mains failure the UPS switches to battery operation with a transfer<br />

time of 4 milliseconds, sufficiently short for computers which therefore will<br />

continue to operate without interruption.<br />

Technical specifications (general)<br />

Input voltage range 500-1500 VA models, 70% load<br />

165-275 Vac<br />

Input voltage range 2200-3000 VA models, 70% load<br />

140-305 Vac<br />

Input frequency 50 or 60 Hz ± 5%<br />

Output voltage<br />

230 Vac ± 2% (battery operation)<br />

Output frequency<br />

50 or 60 Hz, autosensing<br />

Ambient operating temperature -10 to 40°C<br />

Relative humidity<br />

95% non-condensing<br />

Audible noise<br />

35-45 dB(A)<br />

Communication interface<br />

RS232; Plug and Play; open collector alarm contacts (model dependent)<br />

Protection degree<br />

IP20<br />

Runtime table (minutes)<br />

Match Series model 500 700 700L 1000 1000L 1500 2200 3000<br />

at typical UPS load (75%) 5 11 38 12 25 14 8 8<br />

Watts (1) 60 35 77 185 106 185 185 237 308<br />

180 8 23 69 38 69 69 83 112<br />

300 3 11 40 21 40 40 49 66<br />

420 - 6 27 14 27 27 33 46<br />

600 - - - 8 18 18 22 31<br />

900 - - - - - 9 12 19<br />

1540 - - - - - - 5 8<br />

2100 - - - - - - - 5<br />

(1) Max. power factor Match 500-1500: 0.6; Match 2200/3000: 0.7<br />