UPS<br />

ML Series - line-interactive UPS<br />

Applications<br />

The line-interactive Digital Energy ML Series UPS is used in a wide range of IT,<br />

networking and telecommunications applications. It will protect servers, hubs,<br />

switches and routers, and may also be installed to protect PCs, workstations,<br />

cash registers, fax machines, modems and ISDN adaptors.<br />

Order codes<br />

A<br />

B<br />

X<br />

Function<br />

Providing exceptional cost-critical<br />

protection for electrical equipment<br />

Standards / Marking<br />

Safety: EN 50091-1-1; EN 60950;<br />

EMC: EN 50091-2<br />

Characteristics<br />

The line-interactive ML Series UPS normally supplies the load through a bypass<br />

circuit. Filtering capabilities guard against surges, spikes and high frequency<br />

interferences. The utility also keeps the battery fully charged.<br />

The input voltage window is extremely wide: as long as the input voltage is<br />

within 140-300 Vac (ML 350-700 VA) or between 160-265 Vac (ML 1000 VA)<br />

the Automatic Voltage Regulation (AVR) guarantees an output voltage that is<br />

between 198-265 Vac and acceptable for every modern ICT device.<br />

In case of a mains failure the UPS switches to battery operation with a transfer<br />

time of 4 milliseconds, sufficiently short for computers which therefore will<br />

continue to operate without interruption.<br />

Technical specifications (general)<br />

Input voltage range 350-700 VA models<br />

140-300 Vac<br />

Input voltage range 1000 VA model<br />

160-265 Vac<br />

Input frequency 50Hz ± 10%<br />

Output voltage<br />

230Vac +5% / -10% (battery operation)<br />

Output frequency<br />

50Hz<br />

Ambient operating temperature -10 to 40°C<br />

Relative humidity<br />

95% non-condensing<br />

Audible noise<br />

< 35 dB(A)<br />

Communication interface<br />

RS232<br />

Protection degree<br />

IP20<br />

Runtime table (minutes)<br />

ML Series model 350 500 700 1000<br />

at typical UPS load (75%) 4 5 7 7<br />

Watts (1) 60 25 40 60 85<br />

210 3 8 14 24<br />

300 - 3 7 11<br />

420 - - 3 7<br />

600 - - - 3<br />

(1) Max. power factor 0.6 (0.7 at 90% load)<br />