<strong>IEA</strong> SHC Task 38 <strong>Solar</strong> Air Conditioning <strong>and</strong> Refriger<strong>at</strong>ion Subtask C2-A, November 9, 2009<br />

Figure 8. Simul<strong>at</strong>ed external evapor<strong>at</strong>or temper<strong>at</strong>ures using experimentally measured input d<strong>at</strong>a.<br />

Figure 9. Simul<strong>at</strong>ed external absorber temper<strong>at</strong>ures using experimentally measured input d<strong>at</strong>a.<br />

Both figures show th<strong>at</strong> the dynamic behaviour including small oscill<strong>at</strong>ions is in very good<br />

agreement. As discussed in part I, the temper<strong>at</strong>ure levels are not reproduced s<strong>at</strong>isfactorily<br />

because the thermodynamic steady st<strong>at</strong>e model is a very coarse one only. This is toler<strong>at</strong>ed<br />

because the focus is laid on the dynamics. In Figure 8, the dynamics are being reproduced<br />

very well with only a slight delay of 10s between course of the two temper<strong>at</strong>ures. Figure 9<br />

shows a slightly worse agreement for the cooling w<strong>at</strong>er temper<strong>at</strong>ures, with simul<strong>at</strong>ed values<br />

being approx. 25s ahead of measured ones. Also shown in Figure 9 is the simul<strong>at</strong>ed outlet<br />

temper<strong>at</strong>ure of the absorber, t Ao,sim , for which no measured d<strong>at</strong>a was available. We want to<br />

emphasize th<strong>at</strong> no tuning of the dynamic parameters has been performed up to now: the<br />

dynamic response seems to be very robust according to the sensitivity analysis which has<br />

been shown before.<br />