<strong>IEA</strong> SHC Task 38 <strong>Solar</strong> Air Conditioning <strong>and</strong> Refriger<strong>at</strong>ion<br />

Subtask A Report, D<strong>at</strong>e:…<br />

1600<br />

1400<br />

Frequency<br />

1200<br />

1000<br />

800<br />

600<br />

Output Cold<br />

W<strong>at</strong>er AbCH1<br />

Output Cold<br />

W<strong>at</strong>er AbCH2<br />

400<br />

200<br />

0<br />

6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26<br />

Temper<strong>at</strong>ure [°C]<br />

9000<br />

8000<br />

7000<br />

Frequency<br />

6000<br />

5000<br />

4000<br />

3000<br />

Input <strong>Cooling</strong><br />

W<strong>at</strong>er AbCH1<br />

Input <strong>Cooling</strong><br />

W<strong>at</strong>er AbCH2<br />

2000<br />

1000<br />

0<br />

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36<br />

Temper<strong>at</strong>ure [°C]<br />

Figure 8: Frequency of the oper<strong>at</strong>ion temper<strong>at</strong>ure ranges of both chillers in 2010 <strong>at</strong> serial<br />

connection in the driving circuit. (Values based on one minute average.) Source: Fraunhofer<br />

ISE<br />

6 Experiences / Lessons Learned<br />

As the collector is a pure w<strong>at</strong>er system it is necessary to return he<strong>at</strong> from the storage to the<br />

collector for the anti-freeze protection. Therefore, the pump runs in short intervals (bucket<br />

principle). The d<strong>at</strong>a analysis on an annual base showed th<strong>at</strong> in one year about 10% of the<br />

collector he<strong>at</strong> gain is returned to the collector. In these 10% it is not only included the he<strong>at</strong><br />

for freezing protection but also the losses which appear during the normal collector pump<br />

starts (cold w<strong>at</strong>er in the pipes). It should be kept in mind th<strong>at</strong> in normal collector monitoring<br />

these start losses are not recorded. Rough estim<strong>at</strong>ed: approxim<strong>at</strong>ely 1/2 to 2/3 of the 10%<br />

he<strong>at</strong> losses may be assigned to freezing protection.<br />

As the plant is a pure w<strong>at</strong>er system no he<strong>at</strong> exchanger is installed. Consequently, the<br />