<strong>IEA</strong> SHC Task 38 <strong>Solar</strong> Air Conditioning <strong>and</strong> Refriger<strong>at</strong>ion<br />

Subtask A Report, D<strong>at</strong>e:…<br />

Figure 3: Evacu<strong>at</strong>ed tube collector field <strong>at</strong> the main building of the Technical College<br />

Butzbach. Also an effective shading of the rooms can be achieved by the assembly of the<br />

collectors. Source: Fraunhofer ISE<br />

<br />

3 Control Str<strong>at</strong>egy<br />

The control str<strong>at</strong>egy of the system was realized by one of the project partners (Hindenburg<br />

Consulting). Inform<strong>at</strong>ion on the str<strong>at</strong>egy is not <strong>at</strong> h<strong>and</strong>.<br />

The collector sub-control system for freezing protection runs independently from the overall<br />

system control <strong>and</strong> was prepared by the collector manufacturer Paradigma.<br />

4 Monitoring Equipment<br />

4.1 Installed Equipment<br />

For the system monitoring different measurement devices have been installed. Beside<br />

several temper<strong>at</strong>ure <strong>and</strong> volume flow meters also the specific radiant power is measured by<br />

the help of two irradi<strong>at</strong>ion pyranometers (CMP11); one in horizontal position <strong>and</strong> the other<br />

one in the collector plane. The pressure in the collector circuit is measured as well. Ten<br />

electricity meters record the electrical power input of pumps, absorption chillers, cooling<br />

towers, air h<strong>and</strong>ling units <strong>and</strong> the controller (three-phase electricity counters with 1000<br />

impulses per kWh). The oper<strong>at</strong>ing hours from most pumps <strong>and</strong> some valve engines are<br />

registered as well.<br />

The devices to measure the volume flow r<strong>at</strong>es are multiple-jet impeller w<strong>at</strong>er meters with<br />

impulse transmitter. For measuring the temper<strong>at</strong>ures in the system Pt100 temper<strong>at</strong>ure<br />

sensors (accuracy 1/3 DIN class B) were installed.<br />

The following figure 4 shows all measurement points in the system.