IEA SHC Task 38 Solar Air Conditioning and Refrigeration Subtask A Report, Date:… 4.2 Period of Measurement Every data are measured and saved in daily “historic” files with a time scale 30 seconds. These files were downloaded and analyzed frequently about every week. The data available for the Task 38 monitoring is only the summer 2009 (from June to September). Unfortunately, after this date a few issues prevented us to get the monitoring data (problems with the building owner, and it was not possible to get the monitoring data because of the Sonnenklima insolvency). 5 Monitoring Results 5.1 Annual / Monthly Data The table below shows the energies considered in each loop of the installation. It also shows some of the main performance factors calculated monthly and yearly for the monitoring period: Yearly June July August September Energy [kWh] Energy [kWh] Energy [kWh] Energy [kWh] Energy [kWh] Total Electricity Consumption 351,9 115,0 82,2 84,3 70,4 solar irradiation on collector aperture area 8516,9 3519,0 1584,4 1727,5 1686,0 solar thermal output to hot storage 3404,6 1387,9 795,3 607,3 614,1 hot storage input to cooling machine (ACM) 1693,3 511,9 346,5 447,0 387,8 cold output ACM to cold-storage 915,5 271,0 167,3 252,4 224,8 cold storage output to cold-distribution 869,8 257,5 158,9 239,8 213,6 [-] [-] [-] [-] [-] Collector efficiency (-) 0,40 0,39 0,50 0,35 0,36 Thermal COP (-) 0,53 0,48 0,56 0,58 0,53 Electrical COP (-) 2,24 1,93 2,84 3,03 2,24 During the considered monitoring period about 900 kWh of cold was produced and supplied to the building. The collector efficiency were about 0,40 which is good, but expected because the collectors are evacuated tubes collectors. The performance of the chiller is correct, indeed the yearly average of the thermal COP reaches 0,53. On the other hand, the electrical COP is a little bit lower than it could be expected: the average of the electrical COP for this cooling period reaches 2,24 which is not bad because only the cooling period was considered, but it could be better for a solar cooling installation. Actually this value of electrical COP can be explained because of the use of a drycooler to reject the heat. Indeed its two fans are consuming more than a conventional cooling tower, but it was the only affordable way to avoid every legionella risk.
IEA SHC Task 38 Solar Air Conditioning and Refrigeration Subtask A Report, Date:… 5.2 Analysis of a typical good day: 23th August 2009 The table below summarizes the performances of the installation on 23th August 2009: Ensoleillement 177,56 kWh Energie solaire 60,39 kWh Energie générateur 50,87 kWh Energie Evaporateur 30,66 kWh Total énergie élec utilisée 9,19 kWh Rendement capteurs 34,01 % COP thermique 0,60 COP électrique 3,34 During this day 30,66 kWh of cold was produced and supplied to the building. The collector efficiency were about 0,34 which is good, even if we could have expected a little bit better because the evacuated tubes collectors are used. The performance of the chiller is good, indeed the daily average of the thermal COP reaches 0,60 which is a value which can be expected from this chiller. The average of the electrical COP for this day reaches 3,34 which is good. Of course this value could have been better if another heat rejection system have been used, but this value is still good when a drycooler is used. The chart below shows the temperatures at the input and output of the chiller: Temperatures at the input and output of the chiller
- Page 205 and 206: IEA SHC Task 38 Solar Air Condition
- Page 207 and 208: IEA SHC Task 38 Solar Air Condition
- Page 209 and 210: IEA SHC Task 38 Solar Air Condition
- Page 211 and 212: IEA SHC Task 38 Solar Air Condition
- Page 213 and 214: IEA SHC Task 38 Solar Air Condition
- Page 215 and 216: IEA SHC Task 38 Solar Air Condition
- Page 217 and 218: IEA SHC Task 38 Solar Air Condition
- Page 219 and 220: IEA SHC Task 38 Solar Air Condition
- Page 221 and 222: IEA SHC Task 38 Solar Air Condition
- Page 223 and 224: IEA SHC Task 38 Solar Air Condition
- Page 225 and 226: IEA SHC Task 38 Solar Air Condition
- Page 227 and 228: IEA SHC Task 38 Solar Air Condition
- Page 229 and 230: IEA SHC Task 38 Solar Air Condition
- Page 231 and 232: IEA SHC Task 38 Solar Air Condition
- Page 233 and 234: IEA SHC Task 38 Solar Air Condition
- Page 235 and 236: IEA SHC Task 38 Solar Air Condition
- Page 237 and 238: IEA SHC Task 38 Solar Air Condition
- Page 239: IEA SHC Task 38 Solar Air Condition
- Page 242 and 243: IEA SHC Task 38 Solar Air Condition
- Page 244 and 245: IEA SHC Task 38 Solar Air Condition
- Page 246 and 247: IEA SHC Task 38 Solar Air Condition
- Page 248 and 249: IEA SHC Task 38 Solar Air Condition
- Page 250 and 251: IEA SHC Task 38 Solar Air Condition
- Page 252 and 253: IEA SHC Task 38 Solar Air Condition
- Page 254 and 255: IEA SHC Task 38 Solar Air Condition
- Page 258 and 259: IEA SHC Task 38 Solar Air Condition
- Page 260 and 261: Task 38 Solar Air-Conditioning and
- Page 262 and 263: - - - - - - - - - - -
- Page 264 and 265: - - - - - - - - - - -
- Page 266 and 267: Pompe évaporateur + compteur C3 Dr
- Page 268 and 269: 80 70 Temperature (°C) 60 50 40 3
- Page 270 and 271: Power (kW) 20 19 18 17 16 15 14 13
- Page 272 and 273: Power (kW) 20 19 18 17 16 15 14 13
- Page 274 and 275: Task 38 Solar Air-Conditioning and
- Page 276 and 277: IEA SHC Task 38 Solar Air Condition
- Page 278 and 279: IEA SHC Task 38 Solar Air Condition
- Page 280 and 281: IEA SHC Task 38 Solar Air Condition
- Page 282 and 283: IEA SHC Task 38 Solar Air Condition
- Page 284 and 285: IEA SHC Task 38 Solar Air Condition
- Page 286 and 287: IEA SHC Task 38 Solar Air Condition
- Page 288 and 289: IEA SHC Task 38 Solar Air Condition
- Page 290 and 291: IEA SHC Task 38 Solar Air Condition
- Page 292 and 293: IEA SHC Task 38 Solar Air Condition
- Page 294 and 295: IEA SHC Task 38 Solar Air Condition
- Page 296 and 297: IEA SHC Task 38 Solar Air Condition
- Page 298 and 299: IEA SHC Task 38 Solar Air Condition
- Page 300 and 301: Task 38 Solar Air-Conditioning and
- Page 302 and 303: IEA SHC Task 38 Solar Air Condition
- Page 304 and 305: IEA SHC Task 38 Solar Air Condition
<strong>IEA</strong> SHC Task 38 <strong>Solar</strong> Air Conditioning <strong>and</strong> Refriger<strong>at</strong>ion<br />
Subtask A Report, D<strong>at</strong>e:…<br />
5.2 Analysis of a typical good day: 23th August 2009<br />
The table below summarizes the performances of the install<strong>at</strong>ion on 23th August 2009:<br />
Ensoleillement<br />
177,56 kWh<br />
Energie solaire<br />
60,39 kWh<br />
Energie génér<strong>at</strong>eur<br />
50,87 kWh<br />
Energie Evapor<strong>at</strong>eur 30,66 kWh<br />
Total énergie élec utilisée 9,19 kWh<br />
Rendement capteurs 34,01 %<br />
COP thermique 0,60<br />
COP électrique 3,34<br />
During this day 30,66 kWh of cold was produced <strong>and</strong> supplied to the building. The collector<br />
efficiency were about 0,34 which is good, even if we could have expected a little bit better<br />
because the evacu<strong>at</strong>ed tubes collectors are used.<br />
The performance of the chiller is good, indeed the daily average of the thermal COP reaches<br />
0,60 which is a value which can be expected from this chiller.<br />
The average of the electrical COP for this day reaches 3,34 which is good. Of course this<br />
value could have been better if another he<strong>at</strong> rejection system have been used, but this value<br />
is still good when a drycooler is used.<br />
The chart below shows the temper<strong>at</strong>ures <strong>at</strong> the input <strong>and</strong> output of the chiller:<br />
Temper<strong>at</strong>ures <strong>at</strong> the input <strong>and</strong> output of the chiller