<strong>IEA</strong> SHC Task 38 <strong>Solar</strong> Air Conditioning <strong>and</strong> Refriger<strong>at</strong>ion<br />

Subtask A Report, D<strong>at</strong>e:…<br />

As it can be seen, the system was designed to limit as much as possible the electricity<br />

consumption of the overall install<strong>at</strong>ion. Indeed only 4 pumps are used to run the entire<br />

system (without distribution). Moreover, a simple system always works better than a<br />

complic<strong>at</strong>ed one.<br />

Another point which must be enlightened it the choice of a dry cooler for the system’s he<strong>at</strong><br />

rejection. The “Résidence de Lac” is a building for retired peoples. As a consequence<br />

legisl<strong>at</strong>ion is very drastic concerning the legionella bacteria, <strong>and</strong> a drycooler was the only<br />

affordable way to reject efficiently energy without any restrictive regul<strong>at</strong>ion.<br />

Building:<br />

- Type of building: Retired people residence<br />

- Loc<strong>at</strong>ion: Maclas, France<br />

- In oper<strong>at</strong>ion since 2007<br />

- System oper<strong>at</strong>ed by: SIEL<br />

- Air-conditioned area: 210 m²<br />

- System is used for space cooling <strong>and</strong> he<strong>at</strong>ing (No DHW prepar<strong>at</strong>ion)<br />

System general properties:<br />

- Technology: closed cycle<br />

- Nominal capacity: 10 kWcold<br />

- Type of closed system: Absorption<br />

- Br<strong>and</strong> of chiller unit: Sonnenklima<br />

- Chilled w<strong>at</strong>er applic<strong>at</strong>ion: Fan coils<br />

- Dehumidific<strong>at</strong>ion: no<br />

- He<strong>at</strong> rejection system: dry<br />

<strong>Solar</strong> thermal:<br />

- Collector type: Evacu<strong>at</strong>ed tube<br />

- Br<strong>and</strong> of collector: Thermomax Mazdon 20<br />

- Collector area: 24 m² absorber<br />

- Tilt angle, orient<strong>at</strong>ion: 30°, 15° west<br />

- Collector fluid: w<strong>at</strong>er-glycol<br />

- Typical oper<strong>at</strong>ion temper<strong>at</strong>ure: 75°C driving tempe r<strong>at</strong>ure for chiller oper<strong>at</strong>ion<br />

Configur<strong>at</strong>ion:<br />

- He<strong>at</strong> storage: 0.5 m3 w<strong>at</strong>er<br />

- Cold storage: Buffer w<strong>at</strong>er (80 liters)<br />

- The hot <strong>and</strong> cold backups are not included into the solar project, so they are not<br />

monitored. Indeed, the building is an existing building, so a conventional he<strong>at</strong>er <strong>and</strong><br />

air conditioning system were already used.