<strong>IEA</strong> SHC Task 38 <strong>Solar</strong> Air Conditioning <strong>and</strong> Refriger<strong>at</strong>ion<br />

Subtask A Report, D<strong>at</strong>e:…<br />

<br />

Starting from the nominal cooling capacity of the SorTech chiller, the maximum daily cooling<br />

energy can be determined. A 7.5 kW chiller can yield a maximum of 180 kWh of cooling<br />

energy per day, assuming incessant oper<strong>at</strong>ion. The number of oper<strong>at</strong>ion hours in a solar<br />

cooling system, however, can be limited by the he<strong>at</strong> source. An six-hour long oper<strong>at</strong>ion<br />

would ideally still yield 45 kWh of cooling energy. Figure 5 shows daily cooling energies<br />

between 0 <strong>and</strong> 23 kWh.<br />

The values vary according to the control str<strong>at</strong>egy, which indirectly reacts to the outside<br />

temper<strong>at</strong>ure <strong>and</strong> solar radi<strong>at</strong>ion. In addition, the consumer behaviour must be taken into<br />

account. Constant low values of the cooling capacity imply th<strong>at</strong> the chiller is over-sized for<br />

the system.<br />

Apart from the energy output of the system, it is also very important to look <strong>at</strong> temper<strong>at</strong>ure<br />

levels going in <strong>and</strong> out the adsorption chiller, as the hot side <strong>and</strong> the re-cooling temper<strong>at</strong>ure<br />

levels can drastically influence the performance. Figure 6 shows the inlet <strong>and</strong> outlet<br />

temper<strong>at</strong>ures on all three temper<strong>at</strong>ure levels <strong>at</strong> the chiller for a typical August day. The<br />

monitored outside temper<strong>at</strong>ure <strong>and</strong> solar irradi<strong>at</strong>ion can be found in the lower graph. The<br />

outside temper<strong>at</strong>ure peaked <strong>at</strong> 32°C <strong>and</strong> the solar ir radi<strong>at</strong>ion reached 917 W/m2. Overall, it<br />

was a bright sunny day with a cloudy passage in the afternoon.