IEA SHC Task 38 Solar Air Conditioning and Refrigeration Subtask A Report, Date: November 2010 4.2 Analysis of Typical Days 4.2.1 Cooling period 2009 The 25 th of August 2009 is an average sunny summer day in 2009. The cooling power, driving heat and solar yield are drafted together with the linked respective temperatures. Figure 9: Power characteristics of the CoolCabin on Aug. 25, 2009 At 10:16 a.m. the WFC-SC5 chiller is switched on and is running nearly seven and a half hours without break. The average cooling power alternates between 15 and 10 kW with a matching driving heat power between 20 and 15 kW. Some strong swinging conditions can be observed in the last two-thirds of the cooling period. Referring average temperatures for the driving heat are showed in Figure 9. The heat flow temperature remains in steady conditions throughout the cooling period. It can be observed that the solar yield fits quite well with the delivered cooling load. The recooling water loop coming from the cooling tower is regulated with the valve V6 to control the output cooling power. After two hours of declining temperatures at the radiant ceiling - steady supply and return temperatures of 5°C/14°C are reached. Bad thermal COPs and fluctuating power conditions in the machine are the consequence of the low temperature. These fluctuations can be seen in the recooling loop temperatures, the heat medium power and the cooling power. Following this daily analysis it appears that the plant works how it was designed, but some design decisions as well as some control adjustments are irreproducible. Out of the manufacturing information of the Yasaki chiller WFC-SC5 the thermal COP reaches a value of 0.65 under standard conditions. In the beginning of this day the thermal COP reached stable values around 0.7. Afterwards the machine shows alternating COPs. In average a thermal COP of 0.616 was reached in the whole period. Considering measurement uncertainties and the lower heat medium inlet temperature mentioned before the thermal COP is feasible. The chiller was running very reliable throughout the whole summer 2009. It also brought the expected power level and reached a feasible thermal COP. In the following section a closer look will be set to the free cooling mode in order to check the practical operation behavior and performance. page 11

IEA SHC Task 38 Solar Air Conditioning and Refrigeration Subtask A Report, Date: November 2010 4.2.2 Free cooling The CoolCabin is equipped with a special hydraulic design in order to run on a free cooling mode. This feature is included to ensure the cooling of the office rooms also on days without sunshine. Therefore the chiller is bypassed so that the cooling tower is able to run on wet mode and can serve the cooling load directly. The mode is activated if the outside temperature is falling below 21.5°C and the office still has a cooling demand. Similar to the absorption chiller above a day in August was picked out in order to evaluate the operation behavior of the free cooling mode. In Figure 10 the free cooling power, the solar yield and four temperatures are drafted in a diagram. To be able to compare the solar yield to a standard sunny summer day the solar radiation of the August 25, 2009 is added. It can be seen that the free cooling mode started three times that day, always switching on when the outside temperature falls under 21.5°C and stopping when the outside temperature exceeds the 22°C level. The room temperature stays quite stable throughout the day showing a slight downtrend in a bandwidth between 25°C-23°C. Furthermore the flow and return temperature to the radiant ceiling of the office shows values between 18-16°C/19- 17°C (flow/return). The realized temperature differ ence between flow and return temperature is very small. In total 71 kWh cold were delivered to the office rooms on that day. Figure 10: Free cooling operation performance of the CoolCabin on the Aug. 29, 2009 The cooling power revealed a saw tooth tread design which can also be seen in the developing of the radiant ceiling flow temperature. In Figure 11 the practical operation experience of the August 23, 2009 is marked in a diagram. The room temperature stays stable between 25°C and 23°C. In night times the fr ee cooling mode is activated and running on a poor power level. On the day the chiller is operating at an average power level of 10 kW. The room temperature in this time declines only slightly. page 12

<strong>IEA</strong> SHC Task 38 <strong>Solar</strong> Air Conditioning <strong>and</strong> Refriger<strong>at</strong>ion Subtask A Report, D<strong>at</strong>e: November 2010<br />

4.2 Analysis of Typical Days<br />

4.2.1 <strong>Cooling</strong> period 2009<br />

The 25 th of August 2009 is an average sunny summer day in 2009. The cooling power,<br />

driving he<strong>at</strong> <strong>and</strong> solar yield are drafted together with the linked respective temper<strong>at</strong>ures.<br />

Figure 9: Power characteristics of the CoolCabin on Aug. 25, 2009<br />

At 10:16 a.m. the WFC-SC5 chiller is switched on <strong>and</strong> is running nearly seven <strong>and</strong> a half<br />

hours without break. The average cooling power altern<strong>at</strong>es between 15 <strong>and</strong> 10 kW with a<br />

m<strong>at</strong>ching driving he<strong>at</strong> power between 20 <strong>and</strong> 15 kW. Some strong swinging conditions can<br />

be observed in the last two-thirds of the cooling period. Referring average temper<strong>at</strong>ures for<br />

the driving he<strong>at</strong> are showed in Figure 9. The he<strong>at</strong> flow temper<strong>at</strong>ure remains in steady<br />

conditions throughout the cooling period. It can be observed th<strong>at</strong> the solar yield fits quite well<br />

with the delivered cooling load. The recooling w<strong>at</strong>er loop coming from the cooling tower is<br />

regul<strong>at</strong>ed with the valve V6 to control the output cooling power. After two hours of declining<br />

temper<strong>at</strong>ures <strong>at</strong> the radiant ceiling - steady supply <strong>and</strong> return temper<strong>at</strong>ures of 5°C/14°C are<br />

reached. Bad thermal COPs <strong>and</strong> fluctu<strong>at</strong>ing power conditions in the machine are the<br />

consequence of the low temper<strong>at</strong>ure. These fluctu<strong>at</strong>ions can be seen in the recooling loop<br />

temper<strong>at</strong>ures, the he<strong>at</strong> medium power <strong>and</strong> the cooling power. Following this daily analysis it<br />

appears th<strong>at</strong> the plant works how it was designed, but some design decisions as well as<br />

some control adjustments are irreproducible.<br />

Out of the manufacturing inform<strong>at</strong>ion of the Yasaki chiller WFC-SC5 the thermal COP<br />

reaches a value of 0.65 under st<strong>and</strong>ard conditions. In the beginning of this day the thermal<br />

COP reached stable values around 0.7. Afterwards the machine shows altern<strong>at</strong>ing COPs. In<br />

average a thermal COP of 0.616 was reached in the whole period. Considering<br />

measurement uncertainties <strong>and</strong> the lower he<strong>at</strong> medium inlet temper<strong>at</strong>ure mentioned before<br />

the thermal COP is feasible.<br />

The chiller was running very reliable throughout the whole summer 2009. It also brought the<br />

expected power level <strong>and</strong> reached a feasible thermal COP. In the following section a closer<br />

look will be set to the free cooling mode in order to check the practical oper<strong>at</strong>ion behavior<br />

<strong>and</strong> performance.<br />