<strong>IEA</strong> SHC Task 38 <strong>Solar</strong> Air Conditioning <strong>and</strong> Refriger<strong>at</strong>ion Subtask A Report, D<strong>at</strong>e: November 2010<br />

An overview of all monitored d<strong>at</strong>a points is given in Table 1. The controlling <strong>and</strong> monitoring<br />

issues are done by three programmable logic controllers. Overall 111 points are logged on a<br />

local PC. The access to this d<strong>at</strong>a store is provided by internet <strong>and</strong> a remote control system.<br />

Table 1: D<strong>at</strong>a points of the CoolCabin<br />

Quantity No. Type Accuracy<br />

monitoring / control inputs<br />

temper<strong>at</strong>ure 35 PT1000 class B + calibr<strong>at</strong>ion<br />

pressure 4<br />

huba control, OEM<br />

rel<strong>at</strong>iv-<br />

Drucktransmitter<br />

endvalue ±1.5% FS<br />

temp. dependence ±1.5%/10°C<br />

radi<strong>at</strong>ion 1 SP-Lite / Kipp&Zonen<br />

temp. Dependence +0.15%/°C<br />

directional error ±5% <strong>at</strong> 80°<br />

temp. / rel<strong>at</strong>ive humidity 1 ±0.5% °C / ±3%RH<br />

he<strong>at</strong> meter<br />

(energy/volume/power/flow<br />

r<strong>at</strong>e/return-supply-temp./∆T)<br />

electricity meter<br />

(energy/power)<br />

4 (x7)<br />

6 (x2)<br />

logged control outputs<br />

speed control 2<br />

on/off 3<br />

valve position 5<br />

failure signal / set temp. / …<br />

sum 111<br />

L<strong>and</strong>is + Gyr, UH50,<br />

ultraschall class II; 2+0.02 q p /q% (max 5%)<br />

Görlitz DCi<br />

230V/400V, 65A class I; IEC 62053-21 (±1%)<br />

3.2 Period of Measurement<br />

The monitoring system of the CoolCabin is in oper<strong>at</strong>ion since the commissioning in<br />

September 2008. Additional monitoring equipment for level III was completed in June 2009.<br />

Monitoring is ongoing.<br />

The p<strong>at</strong>ency of d<strong>at</strong>a logging (Fehler! Verweisquelle konnte nicht gefunden werden.) is<br />

very high (>96%). Nameable gaps crop up only when the CoolCabin is out of service. One<br />

problem occurred was a roof avalanche th<strong>at</strong> got down on the radi<strong>at</strong>ion sensor. Consequently<br />

no solar radi<strong>at</strong>ion d<strong>at</strong>a was monitored from Jan10 to April10. The missing d<strong>at</strong>a was<br />

calcul<strong>at</strong>ed out of Q1 using a monthly efficiency of the solar collectors including the he<strong>at</strong><br />

exchanger.<br />