<strong>IEA</strong> SHC Task 38 <strong>Solar</strong> Air Conditioning <strong>and</strong> Refriger<strong>at</strong>ion Subtask A Report, D<strong>at</strong>e: November 2010<br />

2 System Design<br />

In Figure 2 the hydraulic scheme of the installed system in Gröbming is shown. There are<br />

two solar collector fields, one on the ground with 30.2 m 2 <strong>and</strong> the second is integr<strong>at</strong>ed in the<br />

façade with 15.8 m 2 . From the solar collectors the he<strong>at</strong> flows through a he<strong>at</strong> exchanger to the<br />

hot w<strong>at</strong>er storage. Three 1500 liter w<strong>at</strong>er storages connected in series are used to store the<br />

solar energy. Depending on the return temper<strong>at</strong>ure from the he<strong>at</strong> exchanger the medium is<br />

str<strong>at</strong>ified to the hot medium or cold storage. In winter the return flow from the distribution<br />

systems is delivered into storage 1 <strong>and</strong> in summer, when the cooling mode is running, into<br />

storage 3. Out of storage 3 the hot w<strong>at</strong>er can be distributed to different recipients, the<br />

domestic hot w<strong>at</strong>er st<strong>at</strong>ion, the absorption chiller, the swimming pool as well as the space<br />

he<strong>at</strong>ing for the building. This can also be done altern<strong>at</strong>ively from storage 1 or 2 if the<br />

temper<strong>at</strong>ure is sufficient.<br />

Figure 2: Hydraulic scheme of the solar cooling system in Gröbming<br />

From the central distribution st<strong>at</strong>ion the hot w<strong>at</strong>er is spread to the different recipients. In<br />

summer time, when the cooling mode is enabled, the chilled w<strong>at</strong>er is also distributed through<br />

the same central distributor st<strong>at</strong>ion.<br />

The recooling w<strong>at</strong>er loop connects the absorption chiller directly to the wet cooling tower.<br />

The absorption chiller PSC-12 is loc<strong>at</strong>ed outside the building. As a consequence of this<br />

loc<strong>at</strong>ion, twice a year a maintenance worker has to discharge <strong>and</strong> charge the hydraulic<br />

cycles of the absorption chiller as well as of the cooling tower before <strong>and</strong> after the winter<br />

period to avoid freezing damages.<br />

page 4