IEA SHC Task 38 Solar Air Conditioning and Refrigeration Subtask A Report A-D3b, Date: December 2010 System reliability and overall success of the installation The system went into operation in late 2008, monitoring data were available since February 2009. In 2009, several adjustments and tests were made on the system. A continuous system operation with effective cooling was available in July and August 2009. However, the system was still not optimized and the monitored performance was below expectations (e.g., monthly thermal COP of below 0.3; chilling capacity too low). Some monitoring signals were not reliable; e.g., the electrical performance could not be calculated, further monitoring errors occurred in the heat rejection circuit. Before solving the remaining problems, the company SK Sonnenklima went into a insolvency procedure. The system operation stopped end of August 2009 and was not restarted since then (also due to the ongoing insolvency). In the available operation period of the chiller July and August 2009, the system has shown apart from optimizing problems the general ability to reduce the peak-load cooling demand from the chilled water network; pre-cooling was done reliable. Thus, the concept is still promising. Furthermore, the free cooling mode via the cooling tower was also working reliable. Since the insolvency procedure was not closed until August 2010, the further use of the system is not clear yet. Photos Collector; the container with the chiller is in the background Absorption chiller in the container Dry heat rejection, attached to the container Monitoring Data Measured period Monitoring level (according to Task 38 procedure) Monitoring by Person responsible for evaluation Feb 2009 – Aug 2009 (commissioning phase) 3 (planned) Technical University Chemnitz Edo Wiemken (Fraunhofer ISE, Germany) Phone: +49 (0)761 4588 5412 Email: edo.wiemken@ise.fraunhofer.de page 44

IEA SHC Task 38 Solar Air Conditioning and Refrigeration Subtask A Report A-D3b, Date: December 2010 2.13 Spain: Gymnasium of the University of Zaragoza, Zaragoza. Description of the application The installation is located in Zaragoza (Spain) at the indoor sports centre of the University of Zaragoza and it is used to cool a gymnasium. This installation was designed as a consequence of the overheating in the existing solar collectors. In summer, the solar field was oversized because solar power was higher than needed. Type of building Gymnasium Location Zaragoza, Spain In operation since 2007 System operated by University of Zaragoza Air-conditioned area 215 m 2 System used for space heating? No System used for DHW preparation? No General description of the system This solar cooling installation was designed as a consequence of the overheating problems of the existing solar filed used to contribute to the domestic hot water supply of the building. In the summer, to solve this problem and to use this solar waste energy, the chosen solution was the installation of an absorption chiller. Therefore, the solar collector field of the solar airconditioning system has 37.5 m 2 of useful area. Solar radiation is absorbed and transformed into thermal energy to feed a 4.5 kW absorption machine by Rotartica. The installation contains 700 liters of hot water storage and two gas boilers as an auxiliary system, but both have been never used. Two fan coils transfer the chilling power from the evaporator of the absorption machine to the gymnasium. Initially, a dry cooling tower was installed to reject the produced heat of the absorption cycle to the outdoor air. After the analysis of the two first years, and due to the negative influence of the ambient temperature on the COP of the chiller, an open geothermal system was installed as a heat rejection system, to improve the COP and the performance of the chiller. Central air-conditioning unit Technology Closed cycle Nominal capacity 4.5 kW cold Type of closed system Absorption Brand of chiller unit Rotartica 045 Chilled water application Fan coil Dehumidification No Heat rejection system Dry cooling tower and an open geothermal system since 2009 Solar thermal Collector type Brand of collector Collector area Tilt angle, orientation Collector fluid Flat-plate Viessmann 37.5 m 2 aperture area 30°, South Water-glycol page 45

<strong>IEA</strong> SHC Task 38 <strong>Solar</strong> Air Conditioning <strong>and</strong> Refriger<strong>at</strong>ion Subtask A Report A-D3b, D<strong>at</strong>e: December 2010<br />

2.13 Spain: Gymnasium of the University of Zaragoza, Zaragoza.<br />

Description of the applic<strong>at</strong>ion<br />

The install<strong>at</strong>ion is loc<strong>at</strong>ed in Zaragoza (Spain) <strong>at</strong> the indoor sports centre of the University of<br />

Zaragoza <strong>and</strong> it is used to cool a gymnasium. This install<strong>at</strong>ion was designed as a<br />

consequence of the overhe<strong>at</strong>ing in the existing solar collectors. In summer, the solar field<br />

was oversized because solar power was higher than needed.<br />

Type of building Gymnasium<br />

Loc<strong>at</strong>ion Zaragoza, Spain<br />

In oper<strong>at</strong>ion since 2007<br />

System oper<strong>at</strong>ed by University of Zaragoza<br />

Air-conditioned area 215 m 2<br />

System used for space he<strong>at</strong>ing? No<br />

System used for DHW prepar<strong>at</strong>ion? No<br />

General description of the system<br />

This solar cooling install<strong>at</strong>ion was designed as a consequence of the overhe<strong>at</strong>ing problems<br />

of the existing solar filed used to contribute to the domestic hot w<strong>at</strong>er supply of the building.<br />

In the summer, to solve this problem <strong>and</strong> to use this solar waste energy, the chosen solution<br />

was the install<strong>at</strong>ion of an absorption chiller. Therefore, the solar collector field of the solar airconditioning<br />

system has 37.5 m 2 of useful area. <strong>Solar</strong> radi<strong>at</strong>ion is absorbed <strong>and</strong> transformed<br />

into thermal energy to feed a 4.5 kW absorption machine by Rotartica. The install<strong>at</strong>ion<br />

contains 700 liters of hot w<strong>at</strong>er storage <strong>and</strong> two gas boilers as an auxiliary system, but both<br />

have been never used. Two fan coils transfer the chilling power from the evapor<strong>at</strong>or of the<br />

absorption machine to the gymnasium.<br />

Initially, a dry cooling tower was installed to reject the produced he<strong>at</strong> of the absorption cycle<br />

to the outdoor air. After the analysis of the two first years, <strong>and</strong> due to the neg<strong>at</strong>ive influence<br />

of the ambient temper<strong>at</strong>ure on the COP of the chiller, an open geothermal system was<br />

installed as a he<strong>at</strong> rejection system, to improve the COP <strong>and</strong> the performance of the chiller.<br />

Central air-conditioning unit<br />

Technology<br />

Closed cycle<br />

Nominal capacity<br />

4.5 kW cold<br />

Type of closed system<br />

Absorption<br />

Br<strong>and</strong> of chiller unit Rotartica 045<br />

Chilled w<strong>at</strong>er applic<strong>at</strong>ion<br />

Fan coil<br />

Dehumidific<strong>at</strong>ion<br />

No<br />

He<strong>at</strong> rejection system<br />

Dry cooling tower <strong>and</strong> an open geothermal system since<br />

2009<br />

<strong>Solar</strong> thermal<br />

Collector type<br />

Br<strong>and</strong> of collector<br />

Collector area<br />

Tilt angle, orient<strong>at</strong>ion<br />

Collector fluid<br />

Fl<strong>at</strong>-pl<strong>at</strong>e<br />

Viessmann<br />

37.5 m 2 aperture area<br />

30°, South<br />

W<strong>at</strong>er-glycol<br />

page 45