<strong>IEA</strong> SHC Task 38 <strong>Solar</strong> Air Conditioning <strong>and</strong> Refriger<strong>at</strong>ion Subtask A Report A-D3b, D<strong>at</strong>e: December 2010<br />

In order to simplify the install<strong>at</strong>ion <strong>and</strong> maintenance of the roof-top system, dry he<strong>at</strong> rejection<br />

was chosen.<br />

The system is a pilot install<strong>at</strong>ion to gain experiences with<br />

- solar pre-cooling in a process cooling network;<br />

- dry he<strong>at</strong> rejection in combin<strong>at</strong>ion with the installed absorption chiller;<br />

- free cooling mode in winter<br />

- pre-installed contained roof-top system<br />

Detailed planning: SK Sonnenklima<br />

Central process pre-cooling unit<br />

Technology<br />

Nominal capacity<br />

Type of closed system<br />

Br<strong>and</strong> of chiller unit<br />

Chilled w<strong>at</strong>er applic<strong>at</strong>ion<br />

Dehumidific<strong>at</strong>ion<br />

He<strong>at</strong> rejection system<br />

<strong>Solar</strong> thermal<br />

closed cycle<br />

10 kW cold<br />

Absorption<br />

SK Sonnenklima: Suninverse<br />

Process cooling (medical equipment); pre-cooling<br />

none<br />

dry air-cooler<br />

Collector type<br />

evacu<strong>at</strong>ed tube with CPC-mirror<br />

Br<strong>and</strong> of collector<br />

Phönix Sonnenwärme AG<br />

Collector area<br />

33 m 2 aperture<br />

Tilt angle, orient<strong>at</strong>ion<br />

45°, south<br />

Collector fluid<br />

w<strong>at</strong>er-glycol<br />

Typical oper<strong>at</strong>ion temper<strong>at</strong>ure 80°C<br />

Configur<strong>at</strong>ion<br />

He<strong>at</strong> storage<br />

Cold storage<br />

Auxiliary he<strong>at</strong>ing support<br />

Auxiliary he<strong>at</strong>er<br />

Auxiliary chiller<br />

1 m 3 w<strong>at</strong>er-glycol<br />

none<br />

none<br />

none<br />

backbone chilled w<strong>at</strong>er network (el. compression chiller)<br />

System scheme<br />

Freezing protection<br />

Chilled w<strong>at</strong>er network<br />

Absorption chiller<br />

W<strong>at</strong>er-glycol; 10 kW<br />

L<strong>at</strong>er planned: w<strong>at</strong>er<br />

Vacuum tube<br />

collector<br />

33 m²<br />

Storage<br />

1 m³<br />

W<strong>at</strong>erglykol<br />

W<strong>at</strong>er<br />

Dry he<strong>at</strong> rejection<br />

(free-cooling)<br />

Radiological Practice:<br />

Process cooling<br />

Space cooling<br />

System performance<br />

For reasons given below, no performance d<strong>at</strong>a can be given.<br />

page 43