<strong>IEA</strong> SHC Task 38 <strong>Solar</strong> Air Conditioning <strong>and</strong> Refriger<strong>at</strong>ion Subtask A Report A-D3b, D<strong>at</strong>e: December 2010<br />

2.9 Germany: Technical College Butzbach<br />

Description of the applic<strong>at</strong>ion<br />

In the low-energy building of the Technical College, dem<strong>and</strong> for summer air conditioning<br />

arises due to high occup<strong>at</strong>ion r<strong>at</strong>es <strong>and</strong> frequent use of computer equipment. The building is<br />

used throughout the summer season. Two existing ventil<strong>at</strong>ion systems (supply/return air with<br />

he<strong>at</strong> recovery, 1,250 m³/h air volume flow r<strong>at</strong>e each) are not sufficient to remove the sensible<br />

<strong>and</strong> l<strong>at</strong>ent cooling loads in summer. For this reason, a solar thermally driven chiller plant was<br />

added <strong>and</strong> supported in the frame of the German <strong>Solar</strong>thermie 2000plus funding programme.<br />

The ventil<strong>at</strong>ion units were extended by cooling coils, <strong>and</strong> additionally chilled ceilings <strong>and</strong><br />

cooling panels were installed.<br />

Type of building College building, low energy building<br />

Loc<strong>at</strong>ion Butzbach, Germany<br />

In oper<strong>at</strong>ion since 2008<br />

System oper<strong>at</strong>ed by Technical College Butzbach<br />

Air-conditioned area 335 m 2<br />

System used for space he<strong>at</strong>ing? Yes<br />

System used for DHW prepar<strong>at</strong>ion? No<br />

General description of the system<br />

Two absorption chillers are installed <strong>and</strong> thermally driven with solar he<strong>at</strong> alone. The<br />

condensing boiler is used for space he<strong>at</strong>ing in winter only. Different oper<strong>at</strong>ion modes are<br />

possible with the system:<br />

<br />

<br />

only one chilled w<strong>at</strong>er temper<strong>at</strong>ure level, e.g. for the removal of sensible cooling<br />

loads, is required. In case both chillers are in oper<strong>at</strong>ion, the driving circuits of the<br />

chillers are usually connected in parallel;<br />

one chiller oper<strong>at</strong>es <strong>at</strong> low chilled w<strong>at</strong>er temper<strong>at</strong>ure level for supply air<br />

dehumidific<strong>at</strong>ion <strong>and</strong> cooling, while the other provides chilled w<strong>at</strong>er <strong>at</strong> a higher<br />

temper<strong>at</strong>ure level for the chilled ceilings. In this mode, it is possible to connect the<br />

driving circuits of the chillers in series with the effect of an increased temper<strong>at</strong>ure<br />

difference in this circuit, resulting in a more favourable collector system oper<strong>at</strong>ion.<br />

The evacu<strong>at</strong>ed tube collector system contains pure w<strong>at</strong>er as collector fluid. A special freezing<br />

protection control runs the collector loop in short intervals <strong>at</strong> low ambient temper<strong>at</strong>ures. No<br />

he<strong>at</strong> exchanger is installed in the total he<strong>at</strong> supply system.<br />

System concept <strong>and</strong> overall system control: Hindenburg Consulting (www.hindenburgconsulting.com)<br />

Detailed planning: IGT GmbH<br />

Central air-conditioning unit<br />

Technology<br />

Nominal capacity<br />

Type of closed system<br />

Br<strong>and</strong> of chiller unit<br />

Chilled w<strong>at</strong>er applic<strong>at</strong>ion<br />

closed cycle<br />

2 x 10 kW cold<br />

Absorption<br />

SK Sonnenklima: Suninverse<br />

Supply air cooling <strong>and</strong> dehumidific<strong>at</strong>ion, chilled ceilings<br />