<strong>IEA</strong> SHC Task 38 <strong>Solar</strong> Air Conditioning <strong>and</strong> Refriger<strong>at</strong>ion Subtask A Report A-D3b, D<strong>at</strong>e: December 2010<br />

2.8 France: INES Research Center Offices, Chambéry<br />

Description of the applic<strong>at</strong>ion<br />

The targeted building welcoming the solar cooling applic<strong>at</strong>ion is the PUMA3’s INES research<br />

office. The INES (N<strong>at</strong>ional Institute of <strong>Solar</strong> Energy) was cre<strong>at</strong>ed in 2006 by the public<br />

institutions to promote <strong>and</strong> develop solar technologies in France. To reach these objectives,<br />

the INES is divided into two centers: research, development <strong>and</strong> innov<strong>at</strong>ion on the one h<strong>and</strong>,<br />

<strong>and</strong> training <strong>and</strong> educ<strong>at</strong>ion on the other h<strong>and</strong>. The INES is loc<strong>at</strong>ed in the “Savoie Technolac”<br />

area which is very close to Chambéry in Rhônes-Alpes area (close to the French Alps <strong>and</strong><br />

Lyon). The PUMA3 building is large, but only 3 mezzanine offices are cooled down by the<br />

solar system. The building was cre<strong>at</strong>ed recently so it has a good level of energy efficiency.<br />

Type of building Office building<br />

Loc<strong>at</strong>ion Chambéry, France<br />

In oper<strong>at</strong>ion since April 2009<br />

System oper<strong>at</strong>ed by INES<br />

Air-conditioned area 21m²<br />

System used for space he<strong>at</strong>ing? Yes<br />

System used for DHW prepar<strong>at</strong>ion? Yes<br />

General description of the system<br />

The system is based on an absorption chiller of 4.5 kW coupled with 30 m² fl<strong>at</strong> pl<strong>at</strong>e<br />

collectors. The install<strong>at</strong>ion cools the building in summer, he<strong>at</strong>s it in winter, <strong>and</strong> it is also able<br />

to produce a small amount of domestic hot w<strong>at</strong>er all year long. The 400 liters he<strong>at</strong> storage<br />

tank is included in a packaged device supplied by Clipsol (SSC BlocSol RSD 120). Included<br />

in this device there is also an electric backup <strong>and</strong> all the security devices rel<strong>at</strong>ed to the he<strong>at</strong><br />

storage. Another tank is installed in the system which is ensuring the cold storage in summer<br />

<strong>and</strong> a second he<strong>at</strong> storage in winter. The he<strong>at</strong> rejection is carried out by a horizontal<br />

geothermal field.<br />

Central air-conditioning unit<br />

Technology<br />

Closed cycle<br />

Nominal capacity<br />

4.5 kW cold<br />

Type of closed system<br />

Absorption<br />

Br<strong>and</strong> of chiller unit<br />

ROTARTICA<br />

Chilled w<strong>at</strong>er applic<strong>at</strong>ion<br />

Fan coil<br />

Dehumidific<strong>at</strong>ion<br />

No<br />

He<strong>at</strong> rejection system Geothermal field, exchange area about 138m²<br />

<strong>Solar</strong> thermal<br />

Collector type<br />

Fl<strong>at</strong> pl<strong>at</strong>e collectors<br />

Br<strong>and</strong> of collector<br />

CLIPSOL<br />

Collector area 30m²<br />

Tilt angle, orient<strong>at</strong>ion 30°, 10°<br />

Collector fluid<br />

W<strong>at</strong>er glycol<br />

Typical oper<strong>at</strong>ion temper<strong>at</strong>ure 80°C<br />

Configur<strong>at</strong>ion<br />