<strong>IEA</strong> SHC Task 38 <strong>Solar</strong> Air Conditioning <strong>and</strong> Refriger<strong>at</strong>ion Subtask A Report A-D3b, D<strong>at</strong>e: December 2010<br />

<strong>Solar</strong> thermal<br />

Collector type<br />

Evacu<strong>at</strong>ed tube<br />

Br<strong>and</strong> of collector Thermomax Mazdon 20<br />

Collector area<br />

24 m 2 absorber<br />

Tilt angle, orient<strong>at</strong>ion<br />

30°, 15° west<br />

Collector fluid<br />

w<strong>at</strong>er-glycol<br />

Typical oper<strong>at</strong>ion temper<strong>at</strong>ure 75 °C driving temper<strong>at</strong>ure for chiller oper<strong>at</strong>ion<br />

Configur<strong>at</strong>ion<br />

He<strong>at</strong> storage<br />

0.5 m 3 w<strong>at</strong>er<br />

Cold storage<br />

Buffer w<strong>at</strong>er (80 liters)<br />

Auxiliary he<strong>at</strong>er<br />

none<br />

Use of auxiliary he<strong>at</strong>ing system -<br />

Auxiliary chiller<br />

yes<br />

- type el. Compression chiller<br />

- capacity 3 kW cold<br />

System scheme<br />

System performance<br />

For one cooling season monitored in summer, an average thermal coefficient of performance<br />

of COPth = 0.54 was observed while the collector yield is about 40%. And the electrical<br />

coefficient of performance for the same period is about COPel = 2.5. Focusing on a day with<br />

especially good clim<strong>at</strong>ic conditions, the COPth can reach 0.63, <strong>and</strong> the COPel reached 3.08.<br />

System reliability <strong>and</strong> overall success of the install<strong>at</strong>ion<br />

The main issue for the Maclas install<strong>at</strong>ion was actually an “administr<strong>at</strong>ive” one. Indeed, the<br />

d<strong>at</strong>a transfers were a bit chaotic since they were transferred first by the chiller manufacturer,<br />

<strong>and</strong> then sent to the institution in charge of the monitoring. And because of the solvability<br />

situ<strong>at</strong>ion of the chiller manufacturer, it was not possible to access the d<strong>at</strong>a to calcul<strong>at</strong>e<br />

performances or to check if the install<strong>at</strong>ion is working properly. However, this partial<br />

monitoring led to several conclusions. The strengths of the install<strong>at</strong>ion were: the ability to<br />

cool down the building from 12pm to 18pm (when it was needed), the comp<strong>at</strong>ibility with a dry<br />

page 23