<strong>IEA</strong> SHC Task 38 <strong>Solar</strong> Air Conditioning <strong>and</strong> Refriger<strong>at</strong>ion Subtask A Report A-D3b, D<strong>at</strong>e: December 2010<br />

2.4 Austria: Municipal Administr<strong>at</strong>ion, Vienna<br />

Description of the applic<strong>at</strong>ion<br />

The MA34 solar cooling system was put up in April 2009. It consists of an Adsorption chiller<br />

with dry cooling tower to cool the office building with a peak cooling load of 7.5 kW. The<br />

hybrid cooling tower <strong>and</strong> the solar collectors are placed on the fl<strong>at</strong> roof of the building.<br />

Type of building office building<br />

Loc<strong>at</strong>ion Vienna, Austria<br />

In oper<strong>at</strong>ion since 2009<br />

System oper<strong>at</strong>ed by<br />

Air-conditioned area<br />

System used for space he<strong>at</strong>ing? Yes<br />

System used for DHW prepar<strong>at</strong>ion? No<br />

General description of the system<br />

Main item of the plant is an adsorption chiller with a nominal cooling capacity of 7.5 KW, type<br />

SOL ACS 08. The he<strong>at</strong> rejection is done by a dry cooling tower, type RCS 08, with EC-fan<br />

technology <strong>and</strong> an additional fresh w<strong>at</strong>er spraying system. The drive he<strong>at</strong> for the chiller is<br />

gener<strong>at</strong>ed by 12 universal panel collectors with a total gross surface of 32.40 m ². The fl<strong>at</strong>pl<strong>at</strong>e<br />

collectors are installed in approxim<strong>at</strong>ely 40 ° inclin<strong>at</strong>ion <strong>and</strong> south orient<strong>at</strong>ion on an<br />

existing roof. In the concept no rehe<strong>at</strong>ing is intended by other boilers. The solar he<strong>at</strong> is<br />

stored in a 2000 l solar buffer - the he<strong>at</strong> transfer from the primary to the secondary solar<br />

cycle is made by a layer loading unit. In the cooling mode the chilled w<strong>at</strong>er is stored in a<br />

w<strong>at</strong>er buffer with the capacity of 800 l. Depending on the cooling requirement of the different<br />

rooms the available fan coils are supplied by the w<strong>at</strong>er tank. In winter mode the hydraulic<br />

interconnecting makes a solar thermal support for he<strong>at</strong>ing purposes of the areas possible.<br />

Central air-conditioning unit<br />

Technology<br />

closed cycle<br />

Nominal capacity<br />

7.5 kW cold<br />

Type of closed system<br />

Adsorption<br />

Br<strong>and</strong> of chiller unit Sortech AG / SOL ACS 08<br />

Chilled w<strong>at</strong>er applic<strong>at</strong>ion<br />

Fan coil<br />

Dehumidific<strong>at</strong>ion<br />

no<br />

He<strong>at</strong> rejection system<br />

Dry cooling tower with w<strong>at</strong>er straying system<br />

<strong>Solar</strong> thermal<br />

Collector type<br />

fl<strong>at</strong>-pl<strong>at</strong>e<br />

Br<strong>and</strong> of collector<br />

SOLution<br />

Collector area<br />

62.4 m 2 gross area<br />

Tilt angle, orient<strong>at</strong>ion<br />

40°, South<br />

Collector fluid<br />

w<strong>at</strong>er-glycol<br />

Typical oper<strong>at</strong>ion temper<strong>at</strong>ure 65°C – 70°C driving temper<strong>at</strong>ure for chiller oper<strong>at</strong>ion<br />