<strong>IEA</strong> SHC Task 38 <strong>Solar</strong> Air Conditioning <strong>and</strong> Refriger<strong>at</strong>ion Subtask A Report A-D3b, D<strong>at</strong>e: December 2010<br />

2.3 Austria: SOLID Office Building, Graz<br />

Description of the applic<strong>at</strong>ion<br />

The office building of SOLID was renov<strong>at</strong>ed in 2004 <strong>and</strong> the solar cooling device was<br />

installed in the year 2008. The façade of the office rooms are south <strong>and</strong> west oriented. To<br />

reduce the solar gains external shading devices are installed <strong>at</strong> each glazing. Because of<br />

internal gains <strong>and</strong> ventil<strong>at</strong>ion via windows, active cooling is indispensable. The solar cooling<br />

equipment is installed in a so-called “<strong>Cooling</strong> Cabin” placed under a pergola which is situ<strong>at</strong>ed<br />

in front of the office building as a nice main entrance. The solar collectors are installed on the<br />

roof of this pergola. The hybrid cooling tower is placed on the fl<strong>at</strong> roof of the office building.<br />

The cooling load of the office rooms is taken out via ceiling cooling elements.<br />

Type of building office building<br />

Loc<strong>at</strong>ion Graz, Austria<br />

In oper<strong>at</strong>ion since 2008<br />

System oper<strong>at</strong>ed by SOLID<br />

Air-conditioned area 435 m 2<br />

System used for space he<strong>at</strong>ing? Yes<br />

System used for DHW prepar<strong>at</strong>ion? No<br />

General description of the system<br />

A closed absorption cycle for gener<strong>at</strong>ing cooling energy is employed. Autonomously solar<br />

thermal gener<strong>at</strong>ed he<strong>at</strong> by high temper<strong>at</strong>ure fl<strong>at</strong> pl<strong>at</strong>e collectors is used to regener<strong>at</strong>e the<br />

process. Within the absorption cooling machine w<strong>at</strong>er is used as refrigerant <strong>and</strong> lithium<br />

bromide is used as solvent. The cold w<strong>at</strong>er gener<strong>at</strong>ed by the absorption cooling machine is<br />

used to cover internal <strong>and</strong> external he<strong>at</strong> gains <strong>and</strong> also the he<strong>at</strong> income caused by windowventil<strong>at</strong>ion<br />

in the office rooms. In winter the solar collectors are in assistance to the space<br />

he<strong>at</strong>ing. In summer <strong>and</strong> winter the solar gener<strong>at</strong>ed he<strong>at</strong> is stored in one buffer storage <strong>and</strong><br />

all energy dem<strong>and</strong> is taken out of it. The additional he<strong>at</strong> from the district he<strong>at</strong>ing is not stored<br />

in the tank but directly carried to the space he<strong>at</strong>ing system. A special applic<strong>at</strong>ion is the usage<br />

of the hybrid cooling tower for direct cooling via the ceiling cooling elements.<br />

Central air-conditioning unit<br />

Technology<br />

Nominal capacity<br />

Type of closed system<br />

Br<strong>and</strong> of chiller unit<br />

Chilled w<strong>at</strong>er applic<strong>at</strong>ion<br />

Dehumidific<strong>at</strong>ion<br />

He<strong>at</strong> rejection system<br />

<strong>Solar</strong> thermal<br />

Collector type<br />

Br<strong>and</strong> of collector<br />

Collector area<br />

Tilt angle, orient<strong>at</strong>ion<br />

Collector fluid<br />

Typical oper<strong>at</strong>ion temper<strong>at</strong>ure<br />

closed cycle<br />

17.5 kWcold, 21 kW peak<br />

Absorption<br />

Yazaki WFC SC5<br />

Chilled ceilings<br />

no<br />

Hybrid cooling tower<br />

High temper<strong>at</strong>ure fl<strong>at</strong>-pl<strong>at</strong>e<br />

ÖkoTech Glu<strong>at</strong>mugl HT<br />

60 m 2 gross area<br />

11°, south<br />

w<strong>at</strong>er-glycol<br />

88 °C driving temper<strong>at</strong>ure for chiller oper<strong>at</strong>ion<br />

page 13