<strong>IEA</strong> SHC Task 38 <strong>Solar</strong> Air Conditioning <strong>and</strong> Refriger<strong>at</strong>ion Subtask A Report A-D3b, D<strong>at</strong>e: December 2010<br />

Use of auxiliary he<strong>at</strong>ing system<br />

Auxiliary chiller<br />

Space he<strong>at</strong>ing in winter, DHW <strong>and</strong> cooling<br />

no<br />

System scheme<br />

System performance<br />

An average thermal COP for the period between the 21st of August <strong>and</strong> the end of<br />

September of 0.565 could be reached. Electrical COPs range in daily values from 0.5 to 5<br />

<strong>and</strong> achieve an average value of 3.1. In the period between the 11th <strong>and</strong> 18th of September<br />

no results were monitored due to a d<strong>at</strong>a processing problem of the computer system.<br />

System reliability <strong>and</strong> overall success of the install<strong>at</strong>ion<br />

In the time where the plant was running, it worked quite well. Nevertheless the average<br />

values over a longer time period are still improvable. In the beginning of the cooling season<br />

problems did occur due to the low volume flow of the solar cycle, therefore the mode was<br />

changed to maximum speed. Now the solar pumps are working in summer times without<br />

rpm-regul<strong>at</strong>ion.<br />

During the monitoring period some problems did occur including monitoring <strong>and</strong> control<br />

system problems. The wet cooling tower works very well in the Gröbming clim<strong>at</strong>e. At a<br />

glance the PSC12 Pink chiller fulfilled the promised thermal COPs <strong>at</strong> the different driving,<br />

cooling <strong>and</strong> recooling temper<strong>at</strong>ures. Considering the other parts of the system, such as the<br />

he<strong>at</strong>ing of the swimming pool, the hot storages or the district he<strong>at</strong> the complete hydraulic<br />

scheme gets overloaded <strong>and</strong> not clearly arranged <strong>at</strong> the first look.<br />

Summarizing five main practical suggestions for improvement have been found:<br />

- adapting the control system in order to make clear division between he<strong>at</strong>ing <strong>and</strong><br />

cooling periods<br />

- including the cooling cycle of the DHW priority rule<br />

- excluding the logical test room temper<strong>at</strong>ure >24°C of the control str<strong>at</strong>egy in order to<br />

use the concrete core activ<strong>at</strong>ion as a storage <strong>and</strong> make the control system easier<br />

page 11