<strong>IEA</strong> SHC Task 38 <strong>Solar</strong> Air Conditioning <strong>and</strong> Refriger<strong>at</strong>ion Subtask A Report A-D3b, D<strong>at</strong>e: December 2010<br />

2.2 Austria: Bachler, Gröbming<br />

Description of the applic<strong>at</strong>ion<br />

Absorption chiller with open wet cooling tower to cool 700 m² office building with a peak<br />

cooling load of 8 kW.<br />

Type of building office building<br />

Loc<strong>at</strong>ion Gröbming, Austria<br />

In oper<strong>at</strong>ion since 2007<br />

System oper<strong>at</strong>ed by Bachler HVAC company (own<br />

office building)<br />

Air-conditioned area 700 m 2<br />

System used for space he<strong>at</strong>ing? Yes<br />

System used for DHW prepar<strong>at</strong>ion? Yes<br />

General description of the system<br />

Closed cycle absorption with ammonia/w<strong>at</strong>er as working pair. The system has biomass as<br />

auxiliary he<strong>at</strong>ing for he<strong>at</strong>ing <strong>and</strong> for the absorption machine.<br />

The building is an office building for a HVAC company with 700 m² cooled office area. The<br />

peak cooling load of the building is 9 kW <strong>and</strong> the building is cooled via concrete core<br />

activ<strong>at</strong>ion.<br />

The building has mechanical building ventil<strong>at</strong>ion with he<strong>at</strong> recovery.<br />

The he<strong>at</strong> rejection is wet, open EWK Axima refriger<strong>at</strong>oin with 25 kW.<br />

Central air-conditioning unit<br />

Technology<br />

closed cycle<br />

Nominal capacity<br />

12 kW cold<br />

Type of closed system<br />

Absorption<br />

Br<strong>and</strong> of chiller unit PINK chillii PSC 12<br />

Chilled w<strong>at</strong>er applic<strong>at</strong>ion<br />

Chilled ceilings<br />

Dehumidific<strong>at</strong>ion<br />

no<br />

He<strong>at</strong> rejection system<br />

Wet open<br />

<strong>Solar</strong> thermal<br />

Collector type<br />

fl<strong>at</strong>-pl<strong>at</strong>e<br />

Br<strong>and</strong> of collector<br />

“Neuma-<strong>Solar</strong>” in Kremsmünster, Austria<br />

Collector area<br />

46 m 2 aperture area<br />

Tilt angle, orient<strong>at</strong>ion<br />

45°, south<br />

Collector fluid<br />

w<strong>at</strong>er-glycol<br />

Typical oper<strong>at</strong>ion temper<strong>at</strong>ure 80 °C (driving he<strong>at</strong> for cooling applic<strong>at</strong>ion)<br />

The solar collectors are partly mounted on the ground, partly installed on the façade of the building.<br />

The system is oper<strong>at</strong>ed with a variable flow control.<br />

Configur<strong>at</strong>ion<br />

He<strong>at</strong> storage<br />

Cold storage<br />

Auxiliary he<strong>at</strong>er<br />

3*1.5m³ w<strong>at</strong>er<br />

none<br />

Biomass, 150 kW<br />