<strong>IEA</strong> SHC Task 38 <strong>Solar</strong> Air Conditioning <strong>and</strong> Refriger<strong>at</strong>ion Subtask A Report A-D3b, D<strong>at</strong>e: December 2010<br />

liter fresh w<strong>at</strong>er have been consumed this corresponds to 70 l fresh w<strong>at</strong>er per hour of<br />

full load oper<strong>at</strong>ion. The open wet cooling tower did supply cooling w<strong>at</strong>er temper<strong>at</strong>ures<br />

below 20°C a couple of days, e.g. the direct use of this cooling w<strong>at</strong>er for the chilled<br />

ceiling circuit is technically reasonable.<br />

- The solar thermal system - composed of 40.50 m² fl<strong>at</strong>-pl<strong>at</strong>e collectors <strong>and</strong> 2000 liter<br />

str<strong>at</strong>ifying hot w<strong>at</strong>er tank - gener<strong>at</strong>es sufficient driving temper<strong>at</strong>ures for the absorption<br />

chiller. Typically the driving temper<strong>at</strong>ure starts with 75°C <strong>and</strong> decreases to 55°C. The<br />

low flow oper<strong>at</strong>ion str<strong>at</strong>egy for the fl<strong>at</strong>-pl<strong>at</strong>e collectors in the rage below 20 l/h m²<br />

supplies sufficient driving temper<strong>at</strong>ures.<br />

System reliability <strong>and</strong> overall success of the install<strong>at</strong>ion<br />

The monitoring system did oper<strong>at</strong>e reliably. Some measurement d<strong>at</strong>a logging gaps appeared<br />

because of reboot troubles of the d<strong>at</strong>a logging system in case of temporary grid blackouts.<br />

The measurement signals of the pyranometer did not deliver reasonable values <strong>and</strong> the<br />

technical problem could not be solved on site.<br />

During the monitoring period once the absorption chiller produced too low cold w<strong>at</strong>er<br />

temper<strong>at</strong>ures which led to crystalliz<strong>at</strong>ion phenomena of the working fluid. The manufacturer<br />

did maintenance work which means mainly refilling of lithium-bromide <strong>and</strong> recre<strong>at</strong>ion of<br />

vacuum.<br />

Office room air temper<strong>at</strong>ures were measured as well <strong>and</strong> during the monitoring period <strong>and</strong><br />

only some few hot days were identified with office room air temper<strong>at</strong>ures exceeding 26°C.<br />

Consequently the thermal user comfort lead to a high acceptance of the office users.<br />

Photos<br />

Office building of SOLution headquarters<br />

S<strong>at</strong>tledt/ Austria<br />

Technical room equipped with EAW<br />

WEGRACAL SE 15 absorption chiller, hot<br />

<strong>and</strong> cold w<strong>at</strong>er storage tank<br />

Chilled ceiling device<br />

Wet open cooling tower<br />

page 8