04.11.2013 Views

IEA Solar Heating and Cooling Programm - NachhaltigWirtschaften.at

IEA Solar Heating and Cooling Programm - NachhaltigWirtschaften.at

IEA Solar Heating and Cooling Programm - NachhaltigWirtschaften.at

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>IEA</strong> SHC Task 38 <strong>Solar</strong> Air Conditioning <strong>and</strong> Refriger<strong>at</strong>ion Subtask A Report A-D3b, D<strong>at</strong>e: December 2010<br />

2 General Description of Monitored Systems<br />

2.1 Austria: SOLution Headqu<strong>at</strong>ers, S<strong>at</strong>tledt<br />

Description of the applic<strong>at</strong>ion<br />

Type of building office building<br />

Loc<strong>at</strong>ion S<strong>at</strong>tledt, Austria<br />

In oper<strong>at</strong>ion since 2005<br />

System oper<strong>at</strong>ed by SOLution <strong>Solar</strong>technik<br />

GmbH<br />

Air-conditioned area 150 m 2<br />

System used for space he<strong>at</strong>ing? Yes<br />

System used for DHW prepar<strong>at</strong>ion? No<br />

General description of the system<br />

The solar thermally driven absorption cooling system is designed to control the air<br />

temper<strong>at</strong>ure of the SOLution <strong>Solar</strong>technik GmbH headquarter office (150 m² useful area) in<br />

summer <strong>and</strong> winter. The system configur<strong>at</strong>ion allows a solar-autonomous cooling oper<strong>at</strong>ion,<br />

e.g. the driving he<strong>at</strong> for the absorption chiller is only gener<strong>at</strong>ed <strong>and</strong> provided by the solar<br />

system. A gas driven boiler allows test routines <strong>and</strong> as well a significant he<strong>at</strong>ing support in<br />

winter.<br />

Since 2008 the company of SOLution <strong>Solar</strong>technik GmbH has moved to a new headquarter<br />

building. Therefore the solar absorption cooling system has been disassembled <strong>and</strong> the<br />

system is not anymore in oper<strong>at</strong>ion.<br />

Central air-conditioning unit<br />

Technology<br />

closed cycle<br />

Nominal capacity<br />

15 kW cold<br />

Type of closed system<br />

Absorption<br />

Br<strong>and</strong> of chiller unit EAW WEGRACAL SE 15<br />

Chilled w<strong>at</strong>er applic<strong>at</strong>ion<br />

Chilled ceiling<br />

Dehumidific<strong>at</strong>ion<br />

no<br />

He<strong>at</strong> rejection system<br />

Wet open (EWK 036/06 Axima)<br />

<strong>Solar</strong> thermal<br />

Collector type<br />

Br<strong>and</strong> of collector<br />

Collector area<br />

Tilt angle, orient<strong>at</strong>ion<br />

Collector fluid<br />

Typical oper<strong>at</strong>ion temper<strong>at</strong>ure<br />

Configur<strong>at</strong>ion<br />

He<strong>at</strong> storage<br />

Cold storage<br />

Auxiliary he<strong>at</strong>er<br />

Use of auxiliary he<strong>at</strong>ing system<br />

Auxiliary chiller<br />

fl<strong>at</strong>-pl<strong>at</strong>e<br />

SOLution<br />

40,50 m 2 gross<br />

21°, South<br />

w<strong>at</strong>er-glycol<br />

85°C driving temper<strong>at</strong>ure for chiller oper<strong>at</strong>ion<br />

2 m 3 w<strong>at</strong>er<br />

0.8 m³ w<strong>at</strong>er<br />

Gas boiler, 9 kW<br />

Space he<strong>at</strong>ing in winter<br />

none<br />