<strong>IEA</strong> SHC Task 38<br />

Monitoring Procedure<br />

Table 8: Output of the spreadsheet for the calcul<strong>at</strong>ion of enthalpy differences (DH)<br />

Description of d<strong>at</strong>a output<br />

Label<br />

Difference between cooling energy delivered from DEC AHU <strong>and</strong> from<br />

conventional AHU with fixed supply temper<strong>at</strong>ure, m*DH AHU corr<br />

Difference of enthalpy (cooling energy) achieved from cooling coil in<br />

conventional AHU, m*DH AHU CC<br />

Difference of enthalpy (he<strong>at</strong>ing energy) achieved from he<strong>at</strong>ing coil in<br />

conventional AHU, m*DH posthe<strong>at</strong><br />

Difference of enthalpy between inlet (external) air <strong>and</strong> outlet (supply ) air<br />

of conventional AHU, m*DH AHU conv<br />

m*DH AHU DEC cooling<br />

m*DH AHU DEC he<strong>at</strong>ing<br />

ΔH corr<br />

ΔH conv_CC<br />

ΔH posthe<strong>at</strong><br />

ΔH conv_AHU<br />

ΔH AHU_cool<br />

ΔH AHU_he<strong>at</strong><br />

These outputs are the special input on the monitoring procedure for DEC systems.<br />

On their basis the Primary Energy R<strong>at</strong>io for conventional AHU (PER REF) can be calcul<strong>at</strong>ed<br />

as follows:<br />

PER<br />

ref _ DEC<br />

=<br />

∆H<br />

conv _ CC<br />

SPF ⋅ ε<br />

el<br />

∆H<br />

∆H<br />

+<br />

η<br />

boiler<br />

conv _ AHU<br />

posthe<strong>at</strong><br />

⋅ ε<br />

fossil<br />

E<br />

+<br />

elec,conv _ AHU<br />

ε<br />

elec<br />

⎡ kWh<br />

⎢<br />

⎣kWh<br />

th<br />

elec<br />

⎤<br />

⎥<br />

⎦<br />

Eq. 61<br />

The Primary Energy Saving factor f save is calcul<strong>at</strong>ed as for all <strong>Solar</strong> <strong>He<strong>at</strong>ing</strong> <strong>and</strong> <strong>Cooling</strong><br />

systems with PER RES or PER fossil :<br />

PER<br />

f sav, shc = 1−<br />

PER<br />

ref<br />

RES / fossil<br />

Eq. 62<br />

3.4 Summary of the output of the procedure<br />

The monitoring procedure supports the evalu<strong>at</strong>ion of the performance of the monitored<br />

system <strong>and</strong> its comparison with a conventional system. To this purposes, three level of d<strong>at</strong>a<br />

29 99% draft Version