<strong>IEA</strong> SHC Task 38<br />

Monitoring Procedure<br />

3. with post-he<strong>at</strong>ing of supply air in the Reference AHU after the cooling to the dewpoint<br />

for dehumidific<strong>at</strong>ion up to the IDENTICAL supply temper<strong>at</strong>ure as measured in<br />

the DEC-AHU<br />

temper<strong>at</strong>ure [°C]<br />

60<br />

55<br />

50<br />

45<br />

40<br />

35<br />

30<br />

25<br />

20<br />

15<br />

10<br />

5<br />

0<br />

DH conv CC<br />

DH post he<strong>at</strong>ing<br />

5 7 9 11 13 15 17 19<br />

humidity r<strong>at</strong>io [g/kg]<br />

DH DEC<br />

Figure 3-4 Air-tre<strong>at</strong>ment in DEC-AHU (green line) <strong>and</strong> in conventional AHU (blue-red line);<br />

post he<strong>at</strong>ing up to the identical supply temper<strong>at</strong>ure as measured in the DEC-AHU<br />

4. without post-he<strong>at</strong>ing. It is assumed th<strong>at</strong> in the conventional AHU the he<strong>at</strong> dem<strong>and</strong> for<br />

post he<strong>at</strong>ing is for free because any kind of waste he<strong>at</strong> is used (e.g. from CHP plant<br />

or using an additional he<strong>at</strong> recovery wheel or using the waste he<strong>at</strong> of the vapor<br />

compression chiller).<br />

Necessary Input-d<strong>at</strong>a for every time-step are shown in Table 7.<br />

Table 7 Necessary measurements for the calcul<strong>at</strong>ion of the enthalpy differences (DH)<br />

Description of d<strong>at</strong>a input<br />

Label<br />

<strong>He<strong>at</strong>ing</strong> mode<br />

<strong>Cooling</strong> mode<br />

Temper<strong>at</strong>ure of inlet air in the AHU (external air)<br />

Rel<strong>at</strong>ive humidity of inlet air in the AHU (external air)<br />

Temper<strong>at</strong>ure of supply air from the AHU<br />

rel<strong>at</strong>ive humidity of supply air from the AHU<br />

Supply air flow,<br />

<strong>He<strong>at</strong>ing</strong> ON/OFF<br />

<strong>Cooling</strong> ON/OFF<br />

T inlet<br />

rH inlet<br />

T supply<br />

rH supply<br />

Supply air flow<br />

Besides the inputs shown in Table 7, one parameter has to be set: the supply temper<strong>at</strong>ure of<br />

reference AHU if it is considered as fixed.<br />

The values output by this spreadsheet are listed inTable 8.<br />

28 99% draft Version