energy performance analysis of adnan menderes international airport
energy performance analysis of adnan menderes international airport
energy performance analysis of adnan menderes international airport
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
APPENDIX A<br />
DATA TEMPLATES FOR ACTIVITIES IN<br />
DESIGNBUILDER<br />
Table A.1. Data Templates for Activities in DesignBuilder<br />
ACTIVITY<br />
ACTIVITY TEMPLATE<br />
GROUND<br />
FLOOR<br />
AIRPORT_<br />
MEETRM<br />
ARRIVAL DEPARTURE ROOF<br />
AIRPORT_<br />
CIRCULATION<br />
AIRPORT_<br />
CHECK<br />
AIRPORT_<br />
CHECK<br />
ZONE MULTIPLIER 1 1 1 1<br />
DENSITY [ PEOPLE/m²] 0,2 0,2 0,25 0,25<br />
METABOLIC ACTIVITY<br />
FACTOR MEN=1 /<br />
WOMEN=0,85<br />
/CHILDREN=0,75<br />
LIGHT<br />
OFFICE<br />
WORK<br />
LIGHT OFFICE<br />
WORK<br />
STANDING/<br />
WALKING<br />
STANDING/<br />
WALKING<br />
0,90 0,90 0,9 0,90<br />
WINTER CLOTHING [clo] 1 1 1 1<br />
SUMMER CLOTHING [clo] 0,5 0,5 0,5 0,5<br />
DWH CONSUMPTION RATE<br />
[l/m²-day]<br />
HEATING SET POINT<br />
TEMPERATURE ˚C<br />
HEATING SET BACK<br />
TEMPERATURE ˚C<br />
COOLING SET POINT<br />
TEMPERATURE ˚C<br />
COOLING SET BACK<br />
TEMPERATURE ˚C<br />
MECHANICAL VENT.<br />
COOLING ˚C<br />
MECHANICAL MAX IN-OUT<br />
DELTA T ˚C<br />
MIN FRESH AIR [ l/s-<br />
PERSON]<br />
MECH. VENT. PER AREA<br />
[ l/s-m²]<br />
LIGHTING ILLUMINANCE<br />
[lux]<br />
0,06 0,06 0,75 0,75<br />
ENVIRONMENTAL CONTROL<br />
22 18 18 18<br />
12 12 12 12<br />
24 25 23 23<br />
28 28 28 28<br />
10 10 20 20<br />
-50 -50 -50 -50<br />
10 10 10 10<br />
0 0 0 0<br />
300 200 500 500<br />
EQUIPMENT<br />
COMPUTERS NA NA NA NA<br />
OFFICE EQUIPMENT (W/m 2 ) 5 5 15 15<br />
MISCELLANEOUS NA NA NA NA<br />
CATERING NA NA NA NA<br />
PROCESS NA NA NA NA<br />
52