ABSTRACT<br />

ENERGY PERFORMANCE ANALYSIS OF ADNAN MENDERES<br />

INTERNATIONAL AIRPORT (ADM)<br />

Space cooling and heating are needed throughout the year for commercial<br />

buildings and electricity use in these buildings accounts for about one-third <strong>of</strong> the total<br />

<strong>energy</strong> consumption in Turkey. In this study, Adnan Menderes International Airport<br />

(ADM) located in Izmir is simulated with EnergyPlus s<strong>of</strong>tware which is a new<br />

generation building <strong>energy</strong> <strong>analysis</strong> tool. The simulation model is constructed first with<br />

Design Builder and than the measured data are used to compare the model. EnergyPlus<br />

simulations are used in this thesis to help understanding more about the ADM’s<br />

dynamics and evaluate various strategies such as different orientation and heating,<br />

cooling, ventilation and air conditioning (HVAC) system. According to simulation and<br />

different HVAC system results; cooling electricity consumption increases 2.8 times in<br />

each month. According to simulation and east orientation results, heat gains decrease<br />

between 2% and 11% in winter, autumn and spring months and increase between 3%<br />

and 14% in summer months.<br />

Measured data <strong>of</strong> ADM building showed that HVAC system had constituted<br />

almost 80% <strong>of</strong> the total <strong>energy</strong> consumption, according to the average data obtained in<br />

2008. The difference between measured and simulation consumption values are greater<br />

more than 70%. According to simulation results, also there is 2.4 times more electricity<br />

consumption on 18 August when compared to 11 January. Finally, <strong>analysis</strong> showed that<br />

ADM building requires year-round cooling and very little heating.<br />