Federal Signal <strong>UltraVoice</strong><br />
Installation and Operation <strong>Manual</strong><br />
6 Unit Number, BCD least significant digit<br />
7 Sensor Status, Amplifiers 1-4<br />
Bit 1 = Amp 1 (Bit = 1 = Not Active)<br />
Bit 2 = Amp 2<br />
Bit 3 = Amp 3<br />
Bit 4 = Amp 4<br />
8 Sensor Status, Amplifiers 5-8<br />
Bit 1 = Amp 5<br />
Bit 2 = Amp 6<br />
Bit 3 = Amp 7<br />
Bit 4 = Amp 8<br />
9 Sensor Status, Amplifiers 9-12<br />
Bit 1 = Amp 9<br />
Bit 2 = Amp 10<br />
Bit 3 = Amp 11<br />
Bit 4 = Amp 12<br />
10 Sensor Status<br />
Bit 1 = Battery<br />
Bit 2 = Master Current<br />
Bit 3 = Audio B<br />
Bit 4 = Audio A<br />
11 Sensor Status<br />
Bit 1 = Intrusion Cabinet 1<br />
Bit 2 = Not Used<br />
Bit 3 = AC Power<br />
Bit 4 = Charger<br />
12 Sensor Status<br />
Bit 1 = Rotation<br />
Bit 2 = Not Used<br />
Bit 3 = Spare<br />
Bit 4 = False Alarm<br />
13 Terminating Character, always an ASCII semicolon<br />
Example Serial Report String<br />
Received serial report string = ; 0 3 0 0 5 7 ? 1 : > 6 ;<br />
Description of Status Report<br />
; Starting character<br />
0 Siren type MOD6024 (six amplifiers)<br />
3 Function state = 3 corresponding to a Steady siren function<br />
005 Siren site number (0000) (0000) (0101), which equals site number 005<br />
7 Sensor status is (0111), Bit 1 is 1, Amp 1 is bad or not active<br />
Bit 2 is 1, Amp 2 is bad or not active<br />
Bit 3 is 1, Amp 3 is bad or not active<br />
Bit 4 is 0, Amp 4 is active and good<br />
? Sensor status is (1111), Bit 1 is 1, Amp 5 is bad or not active<br />
Bit 2 is 1, Amp 6 is bad or not active<br />
Bit 3 is 1, Amp 7 is bad or not active<br />
Bit 4 is 1, Amp 8 is bad or not active<br />
OPTIONS<br />
77