12.10.2013 Views

UltraVoice Manual - Alerting & Notification

UltraVoice Manual - Alerting & Notification

UltraVoice Manual - Alerting & Notification

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

functions programmed for that code, can<br />

be activated by providing an additional<br />

momentary, dry contact closure<br />

between “COM” and the desired JP14<br />

terminal. Shorting “F1” to “COM” will<br />

activate whatever is programmed for<br />

code #1, shorting “F2” to “COM” will<br />

activate whatever is programmed for<br />

code #2 and so on. A half second<br />

momentary contact duration is required.<br />

To terminate an activated signal before<br />

it runs for the full duration, if desired:<br />

Provide a momentary contact closure<br />

between JP14 “COM” and “F8”<br />

(RESET).<br />

Remote Activation Connections:<br />

JP14 Terminal Function<br />

1 “Common”<br />

2 “F1”<br />

3 “F2”<br />

4 “F3”<br />

5 “F4”<br />

6 “F5”<br />

7 “F6”<br />

8 “F7”<br />

9 “F8”<br />

10 “Common”<br />

3.7 Sensor Inputs<br />

Terminal block JP15 at the bottom of the<br />

system motherboard is the Sensor<br />

Inputs. These are activated by a short to<br />

“Common”.<br />

Sensor Connections:<br />

JP15 Terminal Function<br />

1 “Common”<br />

2 “Spare #1”<br />

3 “Common”<br />

4 “Intrusion”<br />

5 “Common”<br />

Federal Signal <strong>UltraVoice</strong><br />

Installation and Operation <strong>Manual</strong><br />

6 “Solar”<br />

7 “Common”<br />

8 “AC Power”<br />

9 “Common”<br />

10 “600 PTT”<br />

11 “Common”<br />

12 “Spare #2”<br />

ELECTRONIC SIREN CONTROL OPERATION<br />

27<br />

Intrusion: Alerts the controller when one<br />

of the unit‟s doors has been<br />

opened. Low is intrusion pass<br />

Solar: Used to sense operation of<br />

solar power system.<br />

Jumper JP15: pins 5 to 6 and<br />

to enable solar sensing. Solar<br />

mode latches power sense to<br />

prevent low light conditions<br />

from causing failures. For<br />

solar panel test, initiate a<br />

reset, and then a poll.<br />

Immediate good power input<br />

required after a reset to pass.<br />

Jumper JP15 pins 7 to 8 AC<br />

sense is required if solar only<br />

unit.<br />

Spare<br />

1 & 2: Unused inputs for special<br />

functions.<br />

AC<br />

Power: Alerts the controller when the<br />

AC Power has failed. Open is<br />

fail. Closed is pass.<br />

600 Ohm<br />

PTT: Puts the unit in Local P.A.<br />

mode for input of external<br />

audio. Closed is active.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!