Chem. Listy, 102, s265–s1311 (2008) Environmental Chemistry & Technology<br />

ple bags were used for all experiments. Both samples were<br />

analyzed by GC-MS and an overview of obtained odorant<br />

concentrations is given in Table II.<br />

Table I<br />

Odorisation Levels according to TPG 918 01(ref. 2 )<br />

Odorisation<br />

level Olfactory perception Comment<br />

(grade)<br />

0 Odour not detected –<br />

1 Very low intensity Odour threshold<br />

2 Weak odour –<br />

3 Mean odour Warning odour level<br />

4 Strong odour –<br />

5 Very strong odour –<br />

6 Extremely strong Upper limit of intensity<br />

odour<br />

Table II<br />

Samples overview<br />

DMS TBM Total<br />

[mg m –3 ]<br />

Sample 1 <strong>2.</strong>71 3.31 6.02<br />

Sample 2 3.32 4.35 7.67<br />

For the estimation of odorisation level shortened examination<br />

described in technical norm ČSn 38 5550 1 was<br />

applied. In this test the odour threshold (grade 1) is estimated<br />

as a first point and the warning odour level (grade 3)<br />

as a second point. From obtained data (mean value from all<br />

observers mean values) the dependence of odorisation level<br />

on odorant concentration in natural gas was created.<br />

The measurement was carried out by two different<br />

groups of observers.<br />

The first one (GROUP 1), consisted of professional<br />

observers who satisfied the conditions listed in ČSn En<br />

13725 3 for performing the olfactometry measurement.<br />

The second one (GROUP 2), consisted of observers who<br />

are performing the subjective odorisation control in gas distribution<br />

companies.<br />

Obtained data are given in Figs. 1. and <strong>2.</strong> Each of them<br />

represents the dependence of odorisation level on the odorant<br />

concentration in natural gas – air mixture.<br />

Conclusions<br />

Performed measurement shows considerable subjectivity<br />

of an olfactometry measurement of the odorisation<br />

level. While observers from Group 1 respond accurately with<br />

minimal deviations, observers from Group 2 respond in wide<br />

range of dilution with considerably scattered results. This<br />

result is connected with the sensitivity threshold across population<br />

and to some extent with professional deformation of<br />

s488<br />

Fig. 1. Dependence of odorisation level on the odorant concentration<br />

for Sample 1<br />

Fig. <strong>2.</strong> Dependence of odorisation level on the odorant concentration<br />

for Sample 2<br />

employees carrying out the on-site olfactometry odorisation<br />

control of nG at selected points on natural gas grid.<br />

From the data obtained from Group 1, the K value for<br />

the odorant used in samples can be estimated. This value<br />

is considerably lower than the K value, which is currently<br />

used in the Czech Republic (the obtained K value lies under<br />

0.003 mg m –3 comparing to published 0.07 mg m –3 in the<br />

national technical regulation 2 ).<br />

As a main result of accomplished experiments it can be<br />

strictly recommended to prefer objective method for periodic<br />

odorisation control. nowadays gas distribution companies<br />

slowly change the way of odorisation control considering the<br />

objective control as the guarantee of safe gas distribution and<br />

utilization up to end customers.<br />

This work has been partly supported by MSM 604 613<br />

73 04.<br />

REFEREnCES<br />

1. ČSn 38 5550; Odorizace topných plynů, 1986.<br />

<strong>2.</strong> TPG 918 01; Odorizace zemního plynu, 200<strong>2.</strong><br />

3. ČSn En 13 725; Kvalita ovzduší. Stanovení koncentrace<br />

pachových. látek dynamickou olfaktometrií, 2003.