Sludge Treatment Project Engineered Container Retrieval and Transfer System December 2011<br />

K. Outside Air Bypass Damper<br />

1. The Outside Air Bypass Damper is normally closed. Upon failure of the Supply fan or<br />

loss of normal power, loss of supply duct pressure or supply duct flow, the Outside Air<br />

Bypass Damper shall open, and the mixed air dampers close.<br />

L. Prefilter Differential Pressure Monitor:<br />

1. The controller shall monitor the differential pressure across the prefilter.<br />

2. Alarms shall be provided as follows:<br />

a. Prefilter Change Required: Prefilter differential pressure exceeds a user definable<br />

limit (adj.).<br />

M. Final Filter Differential Pressure Monitor:<br />

1. The controller shall monitor the differential pressure across the final filter.<br />

2. Alarms shall be provided as follows:<br />

a. Final Filter failure: Final filter differential pressure falls below a user definable<br />

limit (adj.).<br />

b. Final Filter Change Required: Final filter differential pressure exceeds a user<br />

definable limit (adj.).<br />

N. Return Air Temperature:<br />

1. The controller shall monitor the return air temperature.<br />

2. Alarms shall be provided as follows:<br />

a. High Return Air Temp: If the return air temperature is greater than 90°F (adj.).<br />

b. Low Return Air Temp: If the return air temperature is less than 45°F (adj.).<br />

O. Supply Air Temperature:<br />

1. The controller shall monitor the supply air temperature.<br />

2. Alarms shall be provided as follows:<br />

a. High Supply Air Temp: If the supply air temperature is greater than 120°F (adj.).<br />

b. Low Supply Air Temp: If the supply air temperature is less than 45°F (adj.).<br />

P. Environmental Index:<br />

1. When the zone is occupied, the controller will monitor the deviation of the zone<br />

temperature from the heating or cooling setpoint and calculate a 0 - 100% Environmental<br />

Index which gives an indication of how well the zone is maintaining comfort. The<br />

controller will also calculate the percentage of time since occupancy began that the<br />

Environmental Index is 70% or higher. Optionally, a weighting factor can be configured<br />

to adjust the contribution of the zone to the rollup average index based upon the floor<br />

area of the zone, importance of the zone, or other static criteria.<br />

Hardware Points Software Points<br />

Point Name AI AO BI BO AV BV Sched Trend Alarm<br />

Show On<br />

Graphic<br />

Zone Temp × × ×<br />

Zone Setpoint Adjust × ×<br />

Prefilter Differential Pressure × ×<br />

Final Filter Differential Pressure × ×<br />

Return Air Temp × × ×<br />

Contract 44577 KW Annex - Rev. D 44577-CSI-SPEC-001 230993 - 5