Butech, 2012.pdf
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
12<br />
mechanical features<br />
Table - Technical Properties 40NA 40NF<br />
Test estándar – EN 12825 Type of stringers Type of stringers<br />
U.M. SIN L M P SIN L M P<br />
Coverage: A V D G C<br />
Concentrated load at the center of the panel (2.5 mm deflection) kN 2.8 2.8 3.6 4.0 4.4 4.4 4.9 5.2<br />
Maximum load allowed in the center of the panel kN 4.1 4.1 4.3 4.5 8.2 8.2 8.3 8.4<br />
Uniformly distributed load kN/m 2 15.0 15.0 19.0 23.0 21.0 21.0 24.0 29.0<br />
Class according to EN 12825 1 1 1 1 4 4 5 5<br />
Coverage: F L<br />
Concentrated load at the center of the panel (2.5 mm deflection) kN 3.1 3.1 3.9 4.2 4.6 4.6 5.2 5.5<br />
Maximum load allowed in the center of the panel kN 4.2 4.2 4.4 4.6 8.4 8.4 8.5 8.6<br />
Uniformly distributed load kN/m 2 16.0 16.0 20.0 25.0 23.0 23.0 26.0 31.0<br />
Class according to EN 12825 1 1 1 1 5 5 5 5<br />
Coverage: T R S<br />
Concentrated load at the center of the panel (1 mm deflection) kN 2.4 2.5 2.6 2.7 2.6 2.6 2.7 2.9<br />
Maximum load allowed in the center of the panel kN 3.0 3.0 3.1 3.1 3.1 3.1 3.2 3.3<br />
Uniformly distributed load kN/m 2 10.0 10.0 11.0 13.0 11.0 11.0 12.0 14.0<br />
Note: the breaking load is obtained by multiplying by 2 the maximum load allowed.<br />
13