MORLEY-IAS ZX <strong>Fire</strong> Alarm Control <strong>Panels</strong><br />

7.12 Installing Additional Equipment<br />

• Refer to Section 3.5 Installing Additional Equipment for relevant instructions on fitting loop driver<br />

cards, RS485 / RS232 interface cards, printer module (top panel only) or key switch option.<br />

7.13 Maintenance<br />

• Refer to Section 5 Maintenance for details relating to all ZX10Se FACP maintenance issues.<br />

7.14 Specification<br />

7.14.1 Functional Specifications<br />

Specification Item Values<br />

Enclosure 500mm wide, 1000mm high, 185mm deep.<br />

Sealed to IP30.<br />

Weight 38kg without batteries.<br />

Operating Temperature 0ºC to +40ºC<br />

76.8 kg with 24Ah batteries fitted.<br />

Relative Humidity 85% (non-condensing).<br />

Knockouts (20mm) 24 (top), 24 (bottom).<br />

Sounder Output 4 programmable outputs (x2)<br />

Open- and short-circuit monitored.<br />

6k8, EOL resistors (P/N 170-073-682).<br />

1A maximum output current.<br />

Minimum switched current – 1mA.<br />

Auxiliary Relay 2 volt-free, changeover outputs. Relay 1 configured as<br />

Fault output. Relay 2 configured as <strong>Fire</strong> output. (x2).<br />

Contacts rated at 30V AC/DC, 1A maximum.<br />

Sensor Circuit 1 to 5 plug-in loop driver modules per ZX5Se FACP.<br />

Supports Analogue Addressable devices over a 2-wire<br />

combined power and digital data transmission loop.<br />

Loop output voltage and signalling depends on the loop<br />

driver installed – refer to documentation supplied with the<br />

loop driver.<br />

Maximum loop loading is 460mA.<br />

Monitoring Zones Up to 20 zones with individual LED indicators,<br />

Expandable to 40/80 zones with optional LED indicator<br />

boards per (x2).<br />

Maximum 120 zones – up to 200 software zones (no LED<br />

indicators) – x2.<br />

Table 13 – ZX10Se Functional Specification<br />

Page 48 Document No. 996-174-000-1, Revision: 01 <strong>Installation</strong> <strong>Manual</strong>