MORLEY-IAS ZX <strong>Fire</strong> Alarm Control <strong>Panels</strong><br />
7.12 Installing Additional Equipment<br />
• Refer to Section 3.5 Installing Additional Equipment for relevant instructions on fitting loop driver<br />
cards, RS485 / RS232 interface cards, printer module (top panel only) or key switch option.<br />
7.13 Maintenance<br />
• Refer to Section 5 Maintenance for details relating to all ZX10Se FACP maintenance issues.<br />
7.14 Specification<br />
7.14.1 Functional Specifications<br />
Specification Item Values<br />
Enclosure 500mm wide, 1000mm high, 185mm deep.<br />
Sealed to IP30.<br />
Weight 38kg without batteries.<br />
Operating Temperature 0ºC to +40ºC<br />
76.8 kg with 24Ah batteries fitted.<br />
Relative Humidity 85% (non-condensing).<br />
Knockouts (20mm) 24 (top), 24 (bottom).<br />
Sounder Output 4 programmable outputs (x2)<br />
Open- and short-circuit monitored.<br />
6k8, EOL resistors (P/N 170-073-682).<br />
1A maximum output current.<br />
Minimum switched current – 1mA.<br />
Auxiliary Relay 2 volt-free, changeover outputs. Relay 1 configured as<br />
Fault output. Relay 2 configured as <strong>Fire</strong> output. (x2).<br />
Contacts rated at 30V AC/DC, 1A maximum.<br />
Sensor Circuit 1 to 5 plug-in loop driver modules per ZX5Se FACP.<br />
Supports Analogue Addressable devices over a 2-wire<br />
combined power and digital data transmission loop.<br />
Loop output voltage and signalling depends on the loop<br />
driver installed – refer to documentation supplied with the<br />
loop driver.<br />
Maximum loop loading is 460mA.<br />
Monitoring Zones Up to 20 zones with individual LED indicators,<br />
Expandable to 40/80 zones with optional LED indicator<br />
boards per (x2).<br />
Maximum 120 zones – up to 200 software zones (no LED<br />
indicators) – x2.<br />
Table 13 – ZX10Se Functional Specification<br />
Page 48 Document No. 996-174-000-1, Revision: 01 <strong>Installation</strong> <strong>Manual</strong>