MORLEY-IAS ZX <strong>Fire</strong> Alarm Control <strong>Panels</strong><br />
7.8.2 Mains Cable Glands<br />
• Refer to Section 3.4.1.4 Mains Cable Glands for details of recommended cable glands.<br />
7.9 Battery <strong>Installation</strong><br />
• Refer to Section 4 Standby Battery Calculation for calculating the battery backup size<br />
requirements for both ZX5Se panels used by the ZX10Se configuration to meet your particular<br />
site installation. It is important that you calculate the battery size requirements for each ZX5Se<br />
panel, especially as the backup requirements may differ between the panels. Refer to Table 8 -<br />
Current Rating Chart - ZX5Se.<br />
• The ZX10Se FACP must be backed up with two sets of batteries. If the size of these batteries is<br />
calculated to be in excess of 17Ah then they must be installed in two battery boxes suitable for<br />
<strong>Fire</strong> protection use, such as battery box 797-078, located directly adjacent to the side of the<br />
ZX10Se enclosure to adequately protect the battery cables. Refer to the diagram below.<br />
• Refer to Section 5.2.3 Standby Batteries for a list of recommended batteries.<br />
Do not make the final battery connection until the installation is complete.<br />
Battery lead connections are not power limited.<br />
Before installation:<br />
New batteries require ‘top charging’ prior to being put into service.<br />
Drill suitably-sized holes though enclosure walls and fit grommets<br />
OUT<br />
IN 485<br />
B A B A<br />
TB1<br />
PL1<br />
OUT<br />
IN 485<br />
B A B A<br />
TB1<br />
PL1<br />
124-291<br />
124-291<br />
24Ah 24Ah<br />
24Ah 24Ah<br />
Figure 36 – ZX10Se Battery <strong>Installation</strong> – 17Ah or Greater<br />