ZX <strong>Fire</strong> Alarm Control <strong>Panels</strong> MORLEY-IAS<br />
Specification Item Values<br />
Input Voltage 230V 48-62 Hz AC<br />
Voltage tolerance + 10% - 15%<br />
Incoming mains fuse FS1 T 3.15A 250V H 20mm - Chassis mounted.<br />
Power supply card input 16V AC (panel supply) from integral mains transformer.<br />
9V AC (charger & printer supply) from integral mains<br />
transformer.<br />
Power supply card fuses F1 T 10A 250V H 20 mm<br />
F2 T 6.3A 250V H 20 mm<br />
F3 T 6.3A 250V H 20 mm<br />
Charger Rating 1.00 Amp (min) – temperature-compensated, lead-acid battery<br />
charger.<br />
Continuous Power supply<br />
Output Rating<br />
100W total available across 2 outputs:<br />
2<br />
D. C. Output Voltage 25.5V Max & 20V Min<br />
25V Supply (General System) 2.25A (55W) max.<br />
1<br />
35V Supply (Loop Driver feed only) 2.50A (85W) max.<br />
0.75 Amps from the 25V supply is reserved for powering<br />
Internal circuits. The remainder of available power is for<br />
external loads (Conventional sounders, Aux supply & loop<br />
current).<br />
Maximum Ripple Voltage