ZX <strong>Fire</strong> Alarm Control <strong>Panels</strong> MORLEY-IAS<br />

Specification Item Values<br />

Input Voltage 230V 48-62 Hz AC<br />

Voltage tolerance + 10% - 15%<br />

Incoming mains fuse FS1 T 3.15A 250V H 20mm - Chassis mounted.<br />

Power supply card input 16V AC (panel supply) from integral mains transformer.<br />

9V AC (charger & printer supply) from integral mains<br />

transformer.<br />

Power supply card fuses F1 T 10A 250V H 20 mm<br />

F2 T 6.3A 250V H 20 mm<br />

F3 T 6.3A 250V H 20 mm<br />

Charger Rating 1.00 Amp (min) – temperature-compensated, lead-acid battery<br />

charger.<br />

Continuous Power supply<br />

Output Rating<br />

100W total available across 2 outputs:<br />

2<br />

D. C. Output Voltage 25.5V Max & 20V Min<br />

25V Supply (General System) 2.25A (55W) max.<br />

1<br />

35V Supply (Loop Driver feed only) 2.50A (85W) max.<br />

0.75 Amps from the 25V supply is reserved for powering<br />

Internal circuits. The remainder of available power is for<br />

external loads (Conventional sounders, Aux supply & loop<br />

current).<br />

Maximum Ripple Voltage