Morley Fire Panels Installation Manual - Smiths Technical Systems
Morley Fire Panels Installation Manual - Smiths Technical Systems
Morley Fire Panels Installation Manual - Smiths Technical Systems
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
ZX <strong>Fire</strong> Alarm Control <strong>Panels</strong> MORLEY-IAS<br />
Specification Item Values<br />
Enclosure 500mm wide, 500mm high, 183 mm deep.<br />
Sealed to IP30.<br />
Weight 19 kg without batteries.<br />
Operating Temperature 0°C to +40°C<br />
38.8 kg with 24Ah batteries fitted.<br />
Relative Humidity 85% (non-condensing)<br />
Knockouts (20mm) 24 (Top), 24 (Bottom)<br />
Sounder Output 4 programmable outputs.<br />
Open- and short-circuit monitored.<br />
6k8, EOL resistors (P/N 170-073-682).<br />
1A maximum output current.<br />
Minimum switched current – 1mA.<br />
Auxiliary Relay 2 volt-free, changeover outputs. Relay 1 configured as Fault<br />
output. Relay 2 configured as <strong>Fire</strong> output.<br />
Contacts rated at 30V AC/DC, 1 Amp maximum.<br />
Minimum switched load – 1mA @ 5V<br />
Sensor Circuit 1 to 5 plug-in loop driver modules per panel.<br />
Supports Analogue Addressable devices over a 2-wire,<br />
combined-power and digital-data, transmission loop.<br />
Loop Output Voltage and Signalling depends on the loop<br />
driver installed – refer to documentation supplied with the<br />
loop driver.<br />
Maximum Loop Loading is 460mA per loop.<br />
Monitoring zones Up to 20 zones with individual LED indicators, expandable to<br />
40 / 80 zones with optional LED indicator boards.<br />
Maximum 120 zones – up to 200 software zones (no LED<br />
indicators).<br />
Table 10 – ZX5Se Functional Specifications<br />
<strong>Installation</strong> <strong>Manual</strong> Document No. 996-174-000-1, Revision: 01 Page 39