6 Specifications<br />
6.1 Functional Specifications<br />
Specification Item Values<br />
Enclosure 400mm wide, 400mm high, 135 mm deep<br />
Sealed to IP30.<br />
Weight 10 kg without batteries.<br />
Operating Temperature 0°C to +40°C<br />
18.5 kg with 12Ah batteries fitted.<br />
Relative Humidity 85% (non-condensing)<br />
Knockouts (20mm) 14 (Top), 2 (Bottom)<br />
Sounder (NAC) Output 2 programmable outputs.<br />
Open- and short-circuit monitored.<br />
6k8, EOL resistors (P/N 170-073-682).<br />
1A maximum output current.<br />
Minimum switched current – 1mA<br />
Auxiliary Relay 2 volt-free, changeover outputs. Relay 1 configured as Fault<br />
output. Relay 2 configured as <strong>Fire</strong> output.<br />
Contacts rated at 24V AC/DC, 1 Amp, 0.6pF maximum.<br />
Minimum switched load – 1mA @ 5V<br />
Sensor Circuit ZX1Se – 1 plug-in loop driver module per panel.<br />
ZX2Se – 1 to 2 plug-in loop driver modules per panel.<br />
Supports Analogue Addressable devices over a 2-wire,<br />
combined-power and digital-data, transmission loop.<br />
Loop Output Voltage and Signalling depends on the loop<br />
driver installed – refer to documentation supplied with the<br />
loop driver.<br />
Maximum Loop Loading is 460mA per loop.<br />
Monitoring zones Up to 20 zones with individual LED indicators.<br />
Maximum 120 zones – up to 200 software zones (no LED<br />
indicators).<br />
Table 9 – ZX1Se / ZX2Se Functional Specifications<br />
Page 38 Document No. 996-174-000-1, Revision: 01 <strong>Installation</strong> <strong>Manual</strong>