MORLEY-IAS ZX <strong>Fire</strong> Alarm Control <strong>Panels</strong><br />
3.4.14 Cable Routing<br />
• Cables should be routed within the enclosure in accordance with the following diagram. Ensure<br />
that power-limited cables are routed separately from AC Mains and non-power-limited cables.<br />
Sounder and<br />
AUX Power<br />
Power Limited.<br />
Relay Outputs<br />
Not Power Limited.<br />
AUX<br />
O/P<br />
SOUNDER<br />
OUTPUTS<br />
POWER<br />
+24V 0V A- A+ B- B+ LIMITED<br />
RS485/RS232<br />
Power Limited<br />
EARTH<br />
BATT<br />
MON<br />
AC<br />
MON<br />
EARTH<br />
+25V<br />
ZX2Se<br />
Only<br />
RELAY 1<br />
SLC Circuits<br />
Power Limited<br />
COM N/C N/O COM N/C N/O<br />
RELAY 1<br />
Page 26 Document No. 996-174-000-1, Revision: 01 <strong>Installation</strong> <strong>Manual</strong><br />
RELAY 2<br />
RELAY 2<br />
AC Mains<br />
Input<br />
ISOLATE<br />
ELSEWHERE<br />
N<br />
L<br />
F1 T 2A H 250V<br />
Fuse 250V A/S<br />
(FS1) 3.15A<br />
Fuse 250V A/S<br />
(FS2) 1.6A<br />
Fuse 250V A/S<br />
(FS3) 5.0A<br />
Sounder, Relay and AUX cables routed to factory-fitted Filter PCB (see table above for colour of wiring)<br />
Figure 25 – Recommended Cable Routing Arrangement – ZX1Se / ZX2Se<br />
AC Mains<br />
FS1 FS2 FS3<br />
RS485/RS232<br />
Power-Limited<br />
SLC Circuits<br />
Power-Limited<br />
Figure 26 – Recommended Cable Routing Arrangement – ZX5Se<br />
COM N/C N/O COM N/C N/O<br />
Sounder and<br />
AUX Power<br />
Power-Limited<br />
Relay Outputs<br />
Non Power-Limited