MORLEY-IAS ZX <strong>Fire</strong> Alarm Control <strong>Panels</strong><br />

3.4.9.3 EMC Compliance<br />

For EMC Compliance, fit<br />

the Ferrite Absorber<br />

supplied with the RS485<br />

Interface board around the<br />

Peripheral (or Panel) Link<br />

cables.<br />

Using crimp rings terminate<br />

the cable screens at the<br />

nearest earth stud on the<br />

inner top surface of the<br />

back box. In order to keep<br />

the earth tails as short as<br />

possible, use an M5 nut to<br />

space the tail crimp rings<br />

from the back box and to<br />

achieve adequate earth<br />

bonding.<br />

The figure opposite shows<br />

the typical arrangement for<br />

a typical installation.<br />

3.4.9.4 Cable Screen – Earth Connections<br />

Connect Earth drain<br />

wire of cables to nearest<br />

earth stud on inner, top<br />

wall of back box<br />

- keep length<br />

as short as possible<br />

Absorber<br />

Affix cable tie<br />

around wires<br />

below ferrite<br />

Figure 23 – RS485 Loop – EMC Absorber <strong>Installation</strong><br />

• During installation of a panel network the consequences of connecting remote grounds together<br />

must be considered.<br />

• When wiring between RS485 cards and/or peripherals if a drain earth wire is available it should<br />

not be bonded to the chassis at both ends of the link.<br />

• The drain earth wire<br />

should only be bonded<br />

to one of the panel<br />

back boxes at the<br />

cable gland or<br />

provided earth studs.<br />

The other end should<br />

not be bonded directly<br />

to the back box but<br />

should be connected<br />

through a nonpolarised<br />

2.2µFcapacitor.<br />

• This arrangement is<br />

shown opposite.<br />

3.4.10 High Integrity Loop<br />

Connect Earth drain<br />

wire of cables to nearest<br />

earth stud on inner, top<br />

wall of back box<br />

- keep length<br />

as short as<br />

possible<br />

Absorber<br />

Capacitor<br />

Absorber<br />

Figure 24 – RS485 Screen – Earth Arrangement<br />

• Hi485 Interface Modules can be used to create a ‘High Integrity’ RS485 Communications Loop<br />

for use on the Panel Network and Peripheral interface links.<br />

• The ‘High Integrity’ Loop provides open and short circuit protection to ensure that information can<br />

still be passed around the loop if a single fault occurs. The loop can be extended to provide a<br />

communications network of up to 12km (39000’) in distance.<br />

• Refer to the Hi485 <strong>Installation</strong> Guide (996-065) for further information.<br />

Page 24 Document No. 996-174-000-1, Revision: 01 <strong>Installation</strong> <strong>Manual</strong>